External Control Connections (Nioc - ABB ACS 600 Hardware Manual

Ac drives us supplement
Hide thumbs Also See for ACS 600:
Table of Contents

Advertisement

External Control
Connections (NIOC)
Terminal Block Size
X21, X22, X23, X25, X26, X27: cables 0.5 to 1.5 mm
(#20 to #16 AWG)
2
X2: cables 0.5 to 2.5 mm
(#20 to #14 AWG)
Control Cable Lead-through Size:
Ø: 2 x 3x2...11 mm (IEC units)
Factory settings of application software
selection B (type code):
DI1: Start, DI2: Stop, DI3: Reverse, DI4:
Acc/Dec 2, DI5,6: Constant speed 1 to 3 select.
1)
Parameter 10.3 must be set to REQUEST.
2)
Operation: 0 = Open, 1 = Closed
DI 5
DI 6
Output
0
0
Set speed through AI1
1
0
Constant Speed 1
0
1
Constant Speed 2
1
1
Constant Speed 3
Connector X28 for RS 485 connection
1
TRANS
2
GND
Link Connections
3
B-
4
A+
5
GND
Power to link
6
+24 V
Connector X29 for RS 485 connection
1
TRANS
FAULT
2
Link Connections
3
B-
A+
4
5
GND
Power to link
6
+24 V
601/604/607 US Supplement
External control connections of ACx 600 with US standard application
software (Factory Macro) are below. External control connections are
different with other application macros and softwares (see Firmware
Manual).
2
rpm
A
Fault
Appendix A – ACS/ACC 600 Technical Data
Programmable I/O
Factory Settings
X21
1
VREF
Reference voltage
1 k Ω < R
< 10 k Ω
2
GND
L
3
AI1+
Speed reference
> 200 k Ω
R
4
AI1-
in
5
AI2+
By default, not in use.
0(4)... 20 mA , R
6
AI2-
in
7
AI3+
By default, not in use.
0(4)... 20 mA , R
8
AI3-
in
9
AO1+
Motor speed 0(4)...20 mA
0...motor nom. speed, R
10
AO1-
11
AO2+
Output current
0(4)...20 mA
0...motor nom. current, R
12
AO2-
X22
1
DI1
Start
2
DI2
Stop
3
DI3
Forward / Reverse
4
DI4
ACCEL/DECEL 1/2
5
DI5
Constant speed select
6
-
Constant speed select
7
+24V
+24 V d.c. max. 100 mA
8
+24V
9
DGND
Digital Ground
X23
1
+24 V
Auxiliary voltage output, non-
isolated, 24 V d.c. 250 mA
2
GND
X25
1
RO11
Relay output 1
Ready
2
RO12
3
RO13
X26
1
RO21
Relay output 2
Running
2
RO22
3
RO23
X27
1
R031
Relay output 3
Fault (-1)
2
R032
3
R033
10 V d.c.
0(2) ... 10 V
= 100 Ω
= 100 Ω
=
< 700 Ω
L
=
< 700 Ω
L
1)
2)
2)
A-11