7.4 Test setup

From the screen CB Type, Iu and In selection ( see chapter 7.3) press the F1 key to enter the Test setup screen.
In the Test setup screen the following selections are available:
Itest as multiple of In (relative current value) and the corresponding value in Ampere (absolute current value)
Phase to be tested (L1, L2, L3, N)
Max time for Itest current generation
It is also possible to realize an automatic sequential test on all phases ( L1 then L2 then L3 and , if present, N) with a specific
selection : L1>L2>L3 or L1>L2>L3>N
Inserted user informations are mentioned in the "User setting" area.
The item has to be selected using   keys or knob.
The value incremental steps can be modified by means of   keys of the selected item.
Example of setting of I test:
Select Itest parameter with the with the arrow "=>".
Press ENTER to change parameter.
Select the required value   keys or knob.
Press ENTER to confirm.
Setup required phase and timeout.
Press F2 (User data) to enter in user information menu.
For each test, it is possible to insert a short Description, trip unit serial number, user name, and note for 124 characters.