5.3 Electrical Characteristics

Power Supply:
Protection fuse:
Maximum power consumption:

5.4 Environmental Characteristics

Operating temperature
Storage temperature
Relative humidity

5.5 Input/Output

5.5.1

Test connector

The TS3 input and output connections are available to the user by means of the frontal "Main Connector" (see chapter 5.7),
to be connected at the extension cable and/or at the test cable (see chapter 4), both supplied with the test device. On this
connector and consequently on the test cable, the following are available:
5.5.1.1 Generated current signal
Trip Unit
In relè
PR1
250 ... 6300 A
AR1/S1
250 ... 6300 A
S2
250 ... 6300 A
PR11x
250 ... 6300 A
PR12x
400 ... 6300 A
PR23x
400 ... 1600 A
PR33x
200 ... 1600 A
Table 1
Accuracy specification
Note1: the max value to generable current Itest is indicated on the display.
I
test
max
=
Ix(*)
min
Note2:
In
relè
Example :
If the In relè is 6300 A, being the Itest max 48300 A, then the Itest max will be 48000/ 6300 = 7.66 In
888.902.6111
115/230Vac one-phase ±15% 50/60Hz (adjustable by the user)
T10AL250V
800VA
+5°C...+45°C
-5°C...+60°C
0%...95% without condensation
Itest
0.1 ... 15 In
0...0.8In
0.1 ... 15 In
0...0.8In
0.1 ... 15 In
0...0.8In
0.1 ... 12 In
0...0.4In
0.1 ... Ix(*) In
0...4830A
0.1 ...15In
0...5540A
0.1 ...15In
0...5540A
,
15
In
TS3
1SDH000670R0002
www.intellirentco.com
|
Scale
Tolerances
0.8...10In
10...15In
3% f.s
0.8...10In
10...15In
3% f.s
0.8...10In
10...15In
3% f.s
0.4...5.In
5...12.In
3% f.s
4830...48300A
3% f.s
5540...24000A
3% f.s
5540...24000A
3% f.s
I test max
94.5 KA
94.5 KA
94.5 KA
75.6 KA
48.3 KA
24 KA
24 KA