General considerations for EMC-conforming assembly and
construction
Electric and electronical devices have to work correctly on site. This is also valid when electro-magnetic
influences affect them in defined and/or expected strength. The devices themselves must not emit
electro-magnetic noises.
Advant Controller components are developed and constructed so that they have a very high noise
immunity. When the wiring and earthing instructions under "System data and system configuration" are
met, an error-free operation is given.
However, there are applications where high electro-magnetic noises must be taken into due
consideration already during the planning phase: e.g. when frequency converters, compressors, small-
power pumps (high inductance) or mediumvoltage switchgear are mounted nearby. An EMC-compatible
earthing concept will also guarantee an error-free operation here.

General principles

There are three important principles to be especially considered:
Keep all connections as short as possible (in particular the earthing conductors)
Use large conductor cross sections (in particular for the earthing conductors)
Create low-impedance, i.e. good and large-sized contacts (in particular for the earthing conductors)
In particular:
vibration-resistant connections
clean metallic contact areas (remove paint, clean surfaces)
if possible, do not use aluminium parts (they oxidize)
solid plug and screw-type connections
earth cable shields with clips on a well-grounded metallic surface
do not use sheath wires
do not use toothed lock washers under screw connections
No!
bad contact
Make a connection between the DIN rails and PE (Protective Earth). For this, use an earthing wire with a
minimum conductor cross section of 10 mm². The wire is connected to the DIN rail with an M6 screw
according to the drawing above. A large-area contact of the DIN rail with the metallic mounting plate
improves the EMC behaviour significantly, as the disturbances can be discharged more effective.

Cable routing

Route cables meeting the standards.
Sort the cables into cable groups (power current cables, power supply cables, signal cables and data
cables)
Rout signal cables and data cables separately from the power cables, i.e. in separate cable ducts or
cable bundles. The distance should be 20 cm or greater.
Lay signal and data cables close to earthed surfaces.
____________________________________________________________________________________________________________
V2
AC500 Hardware
Yes!
good contact
1-54
System data
AC500 / Issued: 05.2007