Mitsubishi Electric CITY MULTI PURY-HP72TNU-A Data Book page 94

Air conditioning systems
Table of Contents

Advertisement

11. M-NET CONTROL
11-4-3-3. MA remote controller, Multi-refrigerant-system, System Controller at TB7/TB3 side, Booster for long M-NET wiring
PURY
OC
OS
TB7
TB7
51
52
CN40
CN41
CN40
CN41
DipSW5-1
DipSW5-1
ON
ON
TB3
TB3
BC controller
53
TB02
PSU
Power supply
202
unit (PSU)
SC*3
(PAC-SC51KUA)
*2 *4
000 or 201
SC
BC controller
(Main)
93
TB02
203
SC*3
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
*2 System controller should connect to TB7 at Outdoor and use power supply unit together in Multi-Refrigerant-System.
For AG-150A-A, 24VDC should be used with the PAC-SC51KUA.
For AE-200A, AE-50A, and EW-50A the power supply unit PAC-SC51KUA is unused.
*3 When multiple system controllers are connected in the system, set the controller with more functions than others as a "main"
controller and others as "sub".
AE-200A, AE-50A, EW-50A, BAC-HD150, and LM-AP are for exclusive use as a "main" system controller and cannot be used as a "sub"
system controller. Make the setting to only one of the system controllers for "prohibition of operation from local remote controller".
*4 The power supply unit is not necessary for AE-200A, AE-50A, EW-50A, BAC-HD150, and LM-AP.
NOTE:
1. Outdoor units OC and OS in one refrigerant circuit system are automatically detected.
OC and OS are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order
of their address.
2. Address should be set to Indoor units, Lossnay and system controller.
3. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and ME remote controller consume the M-NET power for
transmission use. The power balance is needed to consider for long M-NET wiring. Details refer to 11-3. "System configuration
restrictions".
4. Indoor units should be set with a branch number.
5. Assign an address to each of the sub BC controllers which equals the sum of the smallest address of the indoor
units that are connected to each sub BC controller and 50.
6. When a PAR-CT01MAU or PAR-40MAAU is connected to a group, no other MA remote controllers can be connected to the same group.
MEES19K180
PURY
OC
TB7
TB7
91
CN40
CN41
CN40
DipSW5-1
ON
TB3
TB3
Group1
Group 2
Indoor unit
01
02
TB5
TB15
TB5
TB15
*1
SRU
MA R/C
*1
Wireless R/C
Group 31
Group 32
Indoor unit
42
41
TB5
TB5
TB15
142
*1
SRU
ME R/C
*1
Wireless R/C
PURY
OS
OC
TB7
92
97
CN41
CN40
CN41
DipSW5-1
DipSW5-1
ON
ON
TB3
03
TB5
TB15
TB2
Transmission Booster
PAC-SF46EPA-G
Lossnay
Interlocked with
BC controller
(Sub1)
M-NET address 42
43
94
TB5
Hyper Heating Inverter R2-Series
Group 21
30
TB3
TB5
TB15
MA R/C
MA R/C
(Main)
(Sub)
Group 33
Group 34
44
45
TB5
TB15
TB5
TB15
MA R/C
MA R/C
(Main)
MA R/C
(Sub)
92