8-4. Correction by refrigerant piping length

CITY MULTI system can extend the piping flexibly within its limitation for the actual situation. However, a decrease of cooling/
heating capacity could happen correspondently. Using following correction factor according to the equivalent length of the piping
shown at 8-4-1 and 8-4-2, the capacity can be observed. 8-4-3 shows how to obtain the equivalent length of piping.
8-4-1. Cooling capacity correction
PURY-HP72TNU/YNU
1
0.95
0.90
0.85
0.80
0.75
0.70
0.65
0
100
200
0
31
61
Piping equivalent length
PURY-HP96TNU/YNU
1
0.95
0.90
0.85
0.80
0.75
0.70
0.65
0
100
200
0
31
61
Piping equivalent length
PURY-HP120TNU/YNU
1
0.95
0.90
0.85
0.80
0.75
0.70
0.65
0
100
200
0
31
61
Piping equivalent length
PURY-HP144TSNU/YSNU
1
0.95
0.90
0.85
0.80
0.75
0.70
0.65
0
100
200
0
31
61
Piping equivalent length
MEES19K180
Total capacity of indoor unit
36
54
72
108
300
400
500
600 ft.
92
122
153
183 m
Total capacity of indoor unit
48
72
96
144
300
400
500
600 ft.
92
122
153
183 m
Total capacity of indoor unit
60
90
120
180
300
400
500
600 ft.
92
122
153
183 m
Total capacity of indoor unit
72
108
144
216
300
400
500
600 ft.
92
122
153
183 m
PURY-HP192TSNU/YSNU
1
0.95
0.90
0.85
0.80
0.75
0.70
0.65
0
100
200
0
31
61
Piping equivalent length
PURY-HP240TSNU/YSNU
1
0.95
0.90
0.85
0.80
0.75
0.70
0.65
0
100
200
0
31
61
Piping equivalent length
Hyper Heating Inverter R2-Series
Total capacity of indoor unit
96
144
192
288
300
400
500
600 ft.
92
122
153
183 m
Total capacity of indoor unit
120
180
240
360
300
400
500
600 ft.
92
122
153
183 m
67