9. OPTIONAL PARTS

9-3. JOINT KIT "CMY-R160-J1" FOR BC CONTROLLER

Joint kit "CMY-R160-J1" for BC controller is used to combine 2 ports of the BC controller at a PURY/PQRY system so as to
enable down-stream Indoor capacity above P54 as shown in Fig. 1.
The Joint kit include following items:
1
Instruction
2
Joint pipe(Small)
This sheet
1pc
1pc
Please prepare the following items in the field.
2 Joint pipe (for liquid side)
226(8-29/32")
1. Designing CMY-R160-J1 to a PURY/PQRY system
The maximum down-stream Indoor capacity for 1 port of BC
controller is P54. When the down-stream Indoor capacity is
above P54, Joint kit CMY-R160-J1 is needed to combined 2
ports of BC controller to enlarge the capacity, like Group 2 and
3 in Fig. 1.
Maximum 3 Indoor units are allowed to connect to 1 port of BC
controller or 2 combined ports of BC controller using CMY-
R160-J1.
When connecting Indoor units to 1 port of BC controller or 2
combined ports of BC controller using CMY-R160-J1 or CMY-
Y102SS-G2 is applicable, like Group 1 and 2 in Fig. 1
Caution: Mixed cooling and heating mode at the same time for
Indoor units connecting to 1 port or 2 combined ports is not
available.
2. Piping at the installation site
The connection of CMY-R160-J1 to BC controller and pipe leading to Indoor units is referable to Fig. 2. Non-oxidized brazing is
necessary. All piping must be careful to avoid foreign material getting inside.
After piping and air-tight testing, insulation work to the Joint and pipe should be done. Details is available at the Installation Manual.
2
Joint pipe (for liquid side)
Piping to indoor unit
(Non-oxidized brazing)
Fig.2. Connecting CMY-R160-J1
MEES19K180
3
Joint pipe(Large)
4
Cover 1
1pc
2pcs
1
Tape for insulation material sealing
ø9.52(3/8")
ø9.52(3/8")
3
Joint pipe(for gas side)
5
Cover 2
6
Cover 3
1pc for gas side
1pc for Iiquid side
2
Extension pipe for refrigerant circuit
3 Joint pipe (for gas side)
Outdoor/Heat source unit
Joint
CMY-Y102SS-G2
IU
IU
Group1
Total Indoor Capacity
<=P54
IU
Group2
Total Indoor Capacity
P55 to P96
Fig.1. CMY-R160-J1 applying scheme
Cutting point
Have pipe expansion of indoor unit connecting port by
cutting the piping at the cutting point.
Remove burr after cutting the piping to prevent entering
the piping.
Check that there is no crack at the pipe expansion part.
Hyper Heating Inverter R2-Series
7
Band
8
Reducer 1
9
Reducer 2
OD19.05-ID22.2 OD19.05-ID15.88
8pcs
1pc
ø15.88(5/8")
226(8-29/32")
BC controller
Joint kit
CMY-R160-J1
IU
IU
IU
Group3
Indoor Capacity
P72 to P96
50 (2)
20
Cutting point
(13/16)
1pc
mm (in.)
ø15.88(5/8")
IU
mm (in.)
76