Specifications - Mitsubishi Electric CITY MULTI PURY-HP72TNU-A Data Book

Air conditioning systems
Table of Contents

Advertisement

1. SPECIFICATIONS

I.Hyper Heating Inverter R2-Series
1. SPECIFICATIONS
Outdoor Model
Indoor Model
Power source
Cooling capacity
(Nominal)
Power input
(208-230) Current input
(Rated)
Power input
(208-230) Current input
Temp. range of
Indoor
cooling
Outdoor
Heating capacity
(Nominal)
Power input
(208-230) Current input
(Rated)
Power input
(208-230) Current input
Temp. range of
Indoor
heating
Outdoor
Indoor unit
Total capacity
connectable
Model/Quantity
Sound pressure level (measured in anechoic room) *3 dB <A>
Sound power level (measured in anechoic room) *3
Refrigerant
High pressure
piping diameter
Low pressure
Minimum Circuit Ampacity
Maximum Overcurrent Protection
FAN
Type x Quantity
Airflow rate
Control, Driving mechanism
Motor output
*4 External static press.
Compressor
Type x Quantity
Manufacture
Starting method
Motor output
Case heater
Lubricant
External finish
External dimension H x W x D
Protection
High pressure protection
devices
Inverter circuit (COMP./FAN)
Fan motor
Refrigerant
Type x original charge
Control
Net weight
Heat exchanger
HIC circuit (HIC: Heat Inter-Changer)
Defrosting method
Drawing
External
Wiring
Standard
Document
attachment
Accessory
Optional parts
Remarks
Notes:
1.Nominal cooling conditions (Test conditions are based on AHRI 1230)
Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)
2.Nominal heating conditions (Test conditions are based on AHRI 1230)
Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)
3.Cooling mode/Heating mode
4.External static pressure option is available (0.12 in.WG, 0.24 in.WG, 0.32 in.WG/30 Pa, 60 Pa, 80 Pa).
* Due to continuing improvement, above specifications may be subject to change without notice.
MEES19K180
Non-Ducted
*1 BTU/h
kW
kW
A
BTU/h
kW
kW
A
14.6-13.2
W.B.
D.B.
*2 BTU/h
kW
kW
A
BTU/h
kW
kW
A
15.7-14.2
D.B.
W.B.
dB <A>
in. (mm)
in. (mm)
A
A
cfm
3
m
/min
L/s
kW
kW
kW
in.
mm
lbs (kg)
joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-R160-J1,CMY-R201,202,301,306S-G,CMY-R302,303,304,305S-G1
Main BC controller: CMB-P108,1012,1016NU-JA1,CMB-P1016NU-KA1
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
PURY-HP72TNU-A
3-phase 3-wire 208-230 V ±10% 60 Hz
72,000
21.1
5.22
16.0-14.5
69,000
20.2
4.74
59~75°F (15~24°C)
23~126°F (-5~52°C)
80,000
23.4
5.66
17.4-15.7
76,000
22.3
5.12
59~81°F (15~27°C)
-22~60°F (-30~15.5°C)
50~150% of outdoor unit capacity
P04~P96/1~18
56.5/58.0
75.5/77.0
5/8 (15.88) Brazed
3/4 (19.05) Brazed
38-35
60-50
Propeller fan x 2
7,400
210
3,500
Inverter-control, Brushless DC motor
0.46+0.46
0 in.WG (0 Pa)
Inverter scroll hermetic compressor x 1
AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Inverter
4.0
-
MEL46
Pre-coated galvanized steel sheet
<MUNSELL 5Y 8/1>
71-5/8 x 49-1/4 x 29-3/8
1,818 x 1,250 x 745
High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Over-heat protection, Over-current protection
-
R410A x 17 lbs + 10 oz (8.0 kg)
Indoor LEV and BC controller
609 (276)
Salt-resistant cross fin & copper tube
-
Auto-defrost mode (Reversed refrigerant cycle)
KB94C0GY
KE94G811
Installation Manual
Details refer to External Drw
BC controller: CMB-P104,106,108,1012,1016NU-J1
Sub BC controller: CMB-P104,108NU-KB1
Hyper Heating Inverter R2-Series
Ducted
4.91
15.1-13.6
5.36
16.5-14.9
Unit converter
BTU/h
=kW x 3,412
3
cfm
=m
/min x 35.31
lbs
=kg/0.4536
*Above specification data is
subject to rounding variation.