12. PIPING DESIGN
Limitation of the amount of refrigerant to be charged
The above calculation result of the amount of refrigerant to be charged must become below the value in the table below.
Total index of the outdoor units
Maximum refrigerant charge
MEES19K180
HP72
T/YNU
Factory charged
8.0kg
Charged on site
25.5kg
T otal for system
33.5kg
17 lbs
Factory charged
10 oz
56 lbs
Charged on site
4 oz
73 lbs
T otal for system
14 oz
HP96
HP120
HP144
T/YNU
T/YNU
T/YSNU
10.8kg
10.8kg
16.0kg
30.7kg
36.7kg
42.5kg
41.5kg
47.5kg
58.5kg
23 lbs
23 lbs
35 lbs
12 oz
12 oz
5 oz
67 lbs
80 lbs
93 lbs
11 oz
15 oz
12 oz
91 lbs
104 lbs
128 lbs
8 oz
12 oz
16 oz
Hyper Heating Inverter R2-Series
HP192
HP240
T/YSNU
T/YSNU
21.6kg
21.6kg
52.4kg
68.4kg
74.0kg
90.0kg
47 lbs
47 lbs
10 oz
10 oz
115 lbs
150 lbs
9 oz
13 oz
163 lbs
198 lbs
3 oz
7 oz