Start-up and validation test

Contents of this chapter

This chapter describes the start-up, validation test procedure, and validation of the safety
function.

Validation of the safety functions

You must do a validation test to make sure that the safety function operates correctly and
according to the safety requirements.

Competence

The person who does the validation test of the safety function must be a competent person
with expertise and knowledge of the safety function and functional safety. This person must
document and sign the test procedures and report.

Validation procedure

You must do the validation test using the checklist given in this manual:
• at the initial start-up of the safety function
• after changes related to the safety function (wiring, components, safety function -related
parameter settings, etc.)
• after maintenance work related to the safety function.
The validation test must include at least the following steps:
• you must have a validation test plan
• you must test all commissioned functions for proper operation, from each operation
location