Fault tracing
Contents of this chapter
This chapter provides general diagnostics and troubleshooting tips.
General
If you cannot reset the emergency stop function with the emergency stop reset button [S62],
check the reset circuit connections. Refer to the circuit diagrams delivered with the drive.
Use a multimeter to measure the STO circuit connections, if the inverter unit generates one
or more of these faults:
• STO hardware failure (5090)
• Safe torque off 1 loss (FA81)
• Safe torque off 2 loss (FA82)
For more information, see the hardware and firmware manuals.
Emergency stop safety relay
ACS880-07CLC drives with option +Q951+Q984
■
The type of the emergency stop safety relay [A640] is Phoenix Contact PSR-MC34.
This table gives the indications of the Phoenix Contact PSR-MC34 relay:
PWR LED
IN1/2 LED
ON
OFF
ON
ON
K1 LED
K2 LED
OFF
OFF
OFF
OFF
State
All relays are not activated. The sensor circuit is off.
Possible error, see the data sheet of the relay.
The sensor circuit is active. Relays K1 and K2 are
ready to start and await reset/start command.
Fault tracing 47