Huawei NetCol5000 C030H6B20 10020E1 Quick Manual page 9

In-row chilled water smart cooling product
Table of Contents

Advertisement

4
Installing Pipes
4.1
Piping
1. The condensate pump drainpipe and auto-drainpipe should not be connected together to avoid
water in the auto-drainpipe flowing back to the pump, which will cause the pump to be faulty, as
shown in the following figure.
2. Use a 3-way valve to connect the main pipe.
3. The main condensate pipe gradient should be 1:100.
4. Keep at lest 25 mm away from pipe to pipe. Install a pipe support every 2500 mm.
5. Pipes are recommended to be wrapped with heat insulation foam.
Scenario
Pipes Must Be Connected
Top drainage
Water pump drainpipe
Bottom drainage
Auto-drainpipe, water pump drainpipe (if it is
configured)
Main waterway
Unit: mm
Pipe support
4.2
Installing the Humidifier Water Inlet Pipe
This step applies to devices
configured with humidifier.
Reserved connector
Rigid pipe connector
Rigid pipe
Optional Pipes to Be Connected
Auto-drainpipe
N/A
9
Reserved connector
Pagoda connector
Hose clamp
Hose