Removing the Connecting Kit from
3.4
the Front and Rear Plates
NOTE
Screws connecting the adapter plate and cabinet
are M10. Screws connecting the adapter plate and
base are M12.
A manual pallet truck is usually used to transport the cabinet. If a pallet truck is unavailable or not
allowed, transport the cabinet by manpower. Six people are required. Remove the side panel. Four
people carry the cabinet. Force-bearing area is shown in the figure. The other two hold it to prevent
tilting. Then install the side panel.
Leveling and Securing the Cabinet
3.6
Non-anchored installation on an ESD floor
1. Make cable and pipe holes as required (unit: mm).
3.5
Transportation
Depth of the Device
1000 mm
1100 mm
1200 mm
No.
Name
Ports for humidifier water
1
inlet pipe
Ports for signal cables
2
Ports for the water pump
3
and automatic condensate
drainpipe
Ports for the power and
4
PE cables
Outlet for the water outlet
5
Outlet for the water inlet
6
6
Valve of D
897 mm
997 mm
1097 mm
Inner Diameter
60 mm
28 mm
60 mm
43 mm
60 mm
60 mm