Installing The Device - Huawei NetCol5000 C030H6B20 10020E1 Quick Manual

In-row chilled water smart cooling product
Table of Contents

Advertisement

Unit: mm
Front
3

Installing the Device

1. Read the user manual and instructions for product information before installation.
2. The models described in this document are fully configured smart cooling products. If some components
are not configured, skip the corresponding steps.
3. Use fully insulated tools during installation and operation.
4. Only engineers certified by the manufacturer or its agents are allowed to install, commission, and maintain
the smart cooling product. Personal injury or damage to the equipment may occur in the event of improper
handling. Damage incurred in such a manner is beyond the scope of the equipment's warranty.
5. Keep the equipment upright during transportation. Tilting is forbidden.
6. Qualified electricians are required.
Removing the Air Filters
3.1
(1) Screws connecting the adapter plate and cabinet: M10x25
(2) Screws connecting the adapter plate and base: M12x25
(3) Expansion bolts connecting the base and floor: M12x60
(4) EPDM rubber
1. It is recommended that the base be made of
Rear
angle steel, square steel, or channel steel, with a
width of 58 mm and thickness of 4–5 mm.
2. When the width of angle steel is more than 58
mm, it generates interference with cable holes.
Cut a hole in the angle steel to avoid
interference. If the width is less than or equal to
58 mm, this operation is not required.
3. Install a shock absorbing bar (5 mm thick, made
of EPDM rubber) at the bottom of the base.
4. Control the soldering process to prevent an
excessive error.
5. L equals to the depth of the device.
Operator: ____________Date: ____________
Slowly Opening the Exhaust
3.2
Valve to Discharge Nitrogen
4
The device has been charged
0.3–0.5 MPa nitrogen. If no
nitrogen emits, contact
Huawei technical support.