45/54
5

Connectivity interface

J35µP -
RS232
XA
Q1
Fig. 5-1 TLE Scalable Series 40 to 150 - Connectivity Slots and Serial port J35µP – RS232
TLE Scalable Series 40 to 150 has the following equipment's:
Serial Port J35µP - RS232 (see Section 5.1).
-
Customer Interface board (see Section 5.2).
-
3-ph SNMP/WEB plug-in adapter board (see Section 5.3).
-
"IM0305- UVR Control" board (option - see Section 5.4).
-
Connectivity Slots (CONN2, CONN3 and CONN4) ready for the installation of three connectivity boards.
-
Possible connectivity configurations with TLE Series 160 to 500
J35µP - RS232
X A
Fig. 9-2 Connectivity Slots
Note!
The installation of any option board must be performed only by an ABB Service Technician.
Prior to the installation, connection and cabling of any option board the UPS must be completely
powered down and all the power sources that will be connected to the option board must be de-
energized.
Option board shall be connected only to Safety Extra Low Voltage circuits (SELV for IEC-UL-
CSA60950-1): voltage up to 30Vac / 42.4Vpk or 60Vdc maximum and galvanically separated from
AC Mains supply.
Keep SELV cables separated from high voltage cables.
Connectivity Slots
CONN2
CONN3
CONN4
SNMP
Card
Customer
InterfaceI
board
UVR
board
CI
SNMP
UVR (option)
TLE Scalable Series 40 to 150 UL S1
J35µP - RS232
X A
For a Single UPS it's possible to install the following
connectivity boards:
-
max. 3 "Customer Interface" boards;
-
max. 2 "3-ph SNMP/WEB Plug-in Adapter" boards;
-
max. 1 "IM0305 - UVR Control" board.
For an RPA Parallel System (max. 6 UPS) it's possible to install
the following connectivity boards:
-
max. 3 "Customer Interface" boards for each UPS;
-
max. 2 "3-ph SNMP/WEB Plug-in Adapter" boards for RPA
Parallel System;
-
max. 1 "IM0305 - UVR Control" board for each UPS.
UPS Installation Guide / REV-B
Connectivity Slots
CONN2
CONN3
CONN4
SNMP
Card
Customer
InterfaceI
board
UVR
d
boar
CI
SNMP
UVR (option)