26 Operation principle and hardware description
X330
Customer Interface Terminal Block (MBU=0003, ABB contactors)
1
2
11
12
3
4
13
14
5
6
15
16
Below lamp indicators can be found on front door for friendly operation:
QF1 close/open
KM1 close/open
KM2 close/open
KM3 close/open
VFD mode
Bypass mode
Switches for contactor manual operation can be found on the front door as well:
KM1 close/open
KM2 close/open
KM3 close/open
Selector of local/remote/stop mode is also designed.

Operation sequence

In stop mode the 3 contactors cannot be operated anymore.
This section describes how the contactors operated, either manually or by the DCS.

Maintenance to VFD

Check all the enclosures of drive and bypass unit are properly closed and VFD is
ready for operation
Unlock the mode selection switch
Set the mode selection switch to "Local position" or "Remote position"
Lock the mode selection switch
Close KM1
Close KM2
Close QF1.
KM1 Close CMD
KM1 Open CMD
KM2 Close CMD
KM2 Open CMD
KM3 Close CMD
KM3 Open CMD
Control Signal from customer
Internal supply 230 VAC, 2.5 A