5.4.2 Power Cable Specifications

YJV 5-core cables are recommended. When the ambient temperature is 40°C, the
conductor working temperature cannot exceed 90°C.
For the installation torque for power connection of involved electrical parts, see
the specifications of the electrical parts. If the torque is not specified, see the
torque requirements listed in the following table.
Table 5-7 Power cable specifications
Wiring
Terminal
Power input
(L/N)
Power input
(PE)
AC output
(L)
AC output
(N/PE)
Issue 04 (2021-04-13)
Rated
Recommend
Current (A)
ed Cross-
Sectional
Area (mm
160
50
250
95
400
185
630
2 x 185
160
25
250
50
400
95
630
2 x 95
< 10
2.5
10 ≤ I ≤ 40
6
40 < I ≤ 63
10
< 10
2.5
10 ≤ I ≤ 40
6
Copyright © Huawei Technologies Co., Ltd.
Terminal/Bolt
Specifications
2
)
DT-M10
DT-M12
DT-M16
DT-M16
DT-M10
DT-M10
DT-M12
DT-M12
Cord end
terminal
(crimping
screw
specification:
M4)
Cord end
terminal
(crimping
screw
specification:
M4)
Cord end
terminal
(crimping
screw
specification:
M4)
OT-M6
OT-M6
5 Installation Guide
Recommended
Torque (N·m)
27
47
120
120
27
27
47
47
1.2
1.2
1.2
4.5
4.5
49