PDU8000 Modular Precision PDC V2.0
User Manual
Feature
Safe and reliable
Intelligent monitoring
Capacity expansion
Fire linkage

3.5 Technical Specifications

Table 3-2 Technical specifications
Item
H x W x D (mm)
Weight (kg)
Rated operating
voltage (V)
Rated insulation
voltage (V)
Rated frequency
(Hz)
Rated operating
current (A)
Issue 04 (2021-04-13)
Description
Cost-saving and flexible to deliver and deploy thanks
to a compact design
Compatible with cabinets of low to high power density
(Optional) Hot-swap branch switches, making
maintenance and capacity expansion convenient
Certified by CCC, CE, and TL
Proper connection between main metal components in
the power cabinet; resistance less than 0.1 ohm
Hot-swap monitoring board; strong- and weak-current
separation
Strong networking capability for teleindication,
telemetry, telecontrol, and teleadjusting
Real-time monitoring and alarm reporting
(Optional) Temperature monitoring
(Optional) Capacity expansion for hot-swap circuit
breakers with power-on
(Optional) The non-fire extinguishing power supply is
cut off by using 24 V DC before extinguishant is
released.
Specifications
2000 x 600 x 1100, 2000 x 600 x 1200, 2200 x 600 x 1200,
2500 x 600 x 1200
< 450
208/380/400/415 (line voltage)
500
50/60
630/400/250/160