5.4.3
General Input A to G
GENERAL
Note
5–22
Courtesy of NationalSwitchgear.com
PATH: SETPOINTS
S3 DIGITAL INPUTS
ASSIGN DIGITAL
[ ]
INPUT: None
ASSERTED DIGITAL
MESSAGE
INPUT STATE: Closed
INPUT NAME:
MESSAGE
Input A
BLOCK INPUT
MESSAGE
FROM ONLINE: 0 s
GENERAL INPUT A
MESSAGE
CONTROL: Off
PULSED CONTROL RELAY
MESSAGE
DWELL TIME: 0.0 s
ASSIGN CONTROL
MESSAGE
RELAYS (1-5): -----
GENERAL INPUT A
MESSAGE
CONTROL EVENTS: Off
GENERAL INPUT A
MESSAGE
ALARM: Off
ASSIGN ALARM
MESSAGE
RELAYS (2-5): ---5
GENERAL INPUT A
MESSAGE
ALARM DELAY: 0.5 s
GENERAL INPUT A
MESSAGE
ALARM EVENTS: Off
GENERAL INPUT A
MESSAGE
TRIP: Off
ASSIGN TRIP
MESSAGE
RELAYS (1-4): 1---
GENERAL INPUT A
MESSAGE
TRIP DELAY: 5.0 s
If an input is assigned to the Tachometer function, it may not be assigned via the
setpoint.
DIGITAL INPUT
The seven General Input functions are flexible enough to meet most of the desired digital
input requirements. The asserted state and the name of the digital inputs are
programmable. To disable the input functions when the generator is offline, until some
time after the generator is brought online, a block time should be set. The input functions
will be enabled once the block delay has expired. A value of "0 s" for the
block time indicates that the input functions are always enabled while the
ONLINE
generator is offline as well as online.
CHAPTER 5: SETPOINTS
GENERAL INPUT A(G)
Range: None, Input 1 to Input 7. See
note below.
Range: Closed, Open
Range: 12 alphanumeric characters
Range: 0 to 5000 s in steps of 1.
Range: Off, On
Range: 0.0 to 25.0 s in steps of 0.1
Range: Any combination of Relays 1 to
5
Range: Off, On
Range: Off, Latched, Unlatched
Range: Any combination of Relays 2 to
5
Range: 0.1 to 5000.0 s in steps of 0.1
Range: Off, On
Range: Off, Latched, Unlatched
Range: Any combination of Relays 1 to
4
Range: 0.1 to 5000.0 in steps of 0.1
489 GENERATOR MANAGEMENT RELAY – INSTRUCTION MANUAL