GE 469 Manual
GE 469 Manual

GE 469 Manual

Motor management relay
Hide thumbs Also See for 469:
Table of Contents

Advertisement

Quick Links

GE Power Management

TABLE OF CONTENTS

1.1.1
DESCRIPTION .......................................................................................... 1-1
1.1.2
ORDER INFORMATION............................................................................ 1-4
1.1.3
OTHER ACCESSORIES ........................................................................... 1-4
1.2.1
469 SPECIFICATIONS .............................................................................. 1-5
2.1.1
DESCRIPTION .......................................................................................... 2-1
2.1.2
PRODUCT IDENTIFICATION.................................................................... 2-2
2.1.3
INSTALLATION ......................................................................................... 2-3
2.1.4
UNIT WITHDRAWAL AND INSERTION.................................................... 2-4
2.1.5
TERMINAL LOCATIONS ........................................................................... 2-6
2.2.1
TYPICAL WIRING DIAGRAM.................................................................... 2-8
2.2.2
TYPICAL WIRING...................................................................................... 2-9
2.2.3
CONTROL POWER................................................................................... 2-9
2.2.4
PHASE CURRENT INPUTS .................................................................... 2-10
2.2.5
GROUND CURRENT INPUT................................................................... 2-10
2.2.6
DIFFERENTIAL CURRENT INPUTS....................................................... 2-12
2.2.7
VOLTAGE INPUTS.................................................................................. 2-13
2.2.8
DIGITAL INPUTS..................................................................................... 2-13
2.2.9
ANALOG INPUTS.................................................................................... 2-14
2.2.10 ANALOG OUTPUTS................................................................................ 2-14
2.2.11 RTD SENSOR CONNECTIONS.............................................................. 2-15
a DESCRIPTION ........................................................................................ 2-15
b REDUCED RTD LEAD NUMBER APPLICATION ................................... 2-16
c TWO WIRE RTD LEAD COMPENSATION ............................................. 2-17
d GROUNDING OF RTDs .......................................................................... 2-17
2.2.12 OUTPUT RELAYS ................................................................................... 2-18
2.2.13 DRAWOUT INDICATOR.......................................................................... 2-19
2.2.14 RS485 COMMUNICATIONS PORTS ...................................................... 2-20
2.2.15 TYPICAL 2 SPEED MOTOR WIRING ..................................................... 2-21
2.2.16 DIELECTRIC STRENGTH TESTING ...................................................... 2-22
3.1.1
469 FACEPLATE ....................................................................................... 3-1
3.1.2
DISPLAY.................................................................................................... 3-2
3.1.3
LED INDICATORS..................................................................................... 3-2
a 469 STATUS LED INDICATORS............................................................... 3-2
b MOTOR STATUS LED INDICATORS ....................................................... 3-3
c OUTPUT RELAY LED INDICATORS ........................................................ 3-3
3.1.4
RS232 PROGRAM PORT ......................................................................... 3-3
3.1.5
KEYPAD .................................................................................................... 3-4
3.1.6
ENTERING ALPHANUMERIC TEXT......................................................... 3-4
3.1.7
ENTERING +/- SIGNS .............................................................................. 3-4
3.2.1
PROCEDURE ............................................................................................ 3-5
469 Motor Management Relay
i

Advertisement

Table of Contents
loading

Summary of Contents for GE 469

  • Page 1: Table Of Contents

    3.1.1 469 FACEPLATE ..................3-1 3.1.2 DISPLAY....................3-2 3.1.3 LED INDICATORS..................3-2 a 469 STATUS LED INDICATORS............... 3-2 b MOTOR STATUS LED INDICATORS ............3-3 c OUTPUT RELAY LED INDICATORS ............3-3 3.1.4 RS232 PROGRAM PORT ................. 3-3 3.1.5 KEYPAD ....................3-4 3.1.6...
  • Page 2 ALARMS ....................4-1 c BLOCK START ..................4-1 4.1.2 RELAY ASSIGNMENT PRACTICES ............4-2 4.1.3 SETPOINT MESSAGE MAP ..............4-3 4.2 S1 469 SETUP 4.2.1 PASSCODE ....................4-4 a FUNCTION ....................4-4 b ENABLING PASSCODE PROTECTION ........... 4-4 4.2.2 PREFERENCES ..................
  • Page 3 TABLE OF CONTENTS 4.5.2 RELAY RESET MODE ................4-24 a RESETTING THE 469 ................4-24 b EXAMPLE ....................4-24 4.5.3 FORCE OUTPUT RELAY ............... 4-25 4.6 S5 THERMAL MODEL 4.6.1 MOTOR THERMAL LIMITS..............4-26 4.6.2 469 THERMAL MODEL ................4-28 4.6.3...
  • Page 4 EXAMPLE 1 ..................... 4-80 c EXAMPLE 2 ..................... 4-80 4.13.3 ANALOG IN DIFF 1-2 ................4-81 4.13.4 ANALOG IN DIFF 3-4 ................4-82 4.14 S13 469 TESTING 4.14.1 SIMULATION MODE ................4-83 4.14.2 PRE-FAULT SETUP ................4-84 4.14.3 FAULT SETUP..................4-85 4.14.4 TEST OUTPUT RELAYS .................
  • Page 5 USER DEFINABLE MEMORY MAP AREA ..........6-16 6.4.3 EVENT RECORDER ................6-17 6.4.4 WAVEFORM CAPTURE................6-17 6.4.5 469 MEMORY MAP ................. 6-18 6.4.6 469 MEMORY MAP FORMAT CODES ........... 6-61 7. TESTING 7.1 OVERVIEW 7.1.1 TEST SETUP..................... 7-1 GE Power Management 469 Motor Management Relay...
  • Page 6 GROUND (1A/5A) AND DIFFERENTIAL ACCURACY TEST ....7-3 a 5 A INPUT ....................7-3 b 1 A INPUT ....................7-3 7.2.4 GE POWER MANAGEMENT 50:0.025 GROUND ACCURACY TEST ..7-4 7.2.5 RTD ACCURACY TEST ................7-4 7.2.6 DIGITAL INPUTS AND TRIP COIL SUPERVISION ........7-6 7.2.7...
  • Page 7 E. APPENDIX E E.1 FIGURES AND TABLES E.1.1 LIST OF FIGURES ..................E-1 E.1.2 LIST OF TABLES..................E-3 F. APPENDIX F F.1 EU DECLARATION OF CONFORMITY G. WARRANTY G.1 WARRANTY INFORMATION G.1.1 WARRANTY ....................G-1 GE Power Management 469 Motor Management Relay...
  • Page 9: Introduction

    The 469 Motor Management Relay is a microprocessor based relay designed for the protection and manage- ment of medium and large horsepower motors and driven equipment. The 469 is equipped with six output relays for trips, alarms, and start blocks. Motor protection, fault diagnostics, power metering, and RTU func- tions are integrated into one economical drawout package.
  • Page 10 Ground faults or earth leakage as low as 0.25 A may be detected using the GE Power Management 50:0.025 Ground CT. CT inputs for phase differential protection are also provided. The 12 RTD inputs provided may be individually field programmed for different RTD types. Volt- age transformer inputs allow for numerous protection features based on voltage and power quantities.
  • Page 11 LAST TRIP DATA actual values. The 469 event recorder stores up to 40 time and date stamped events including the pre-trip data. Each time a trip occurs, the 469 stores a trace of 8 cycles pre-trip and 8 cycles post-trip for all measured AC quantities.
  • Page 12: Order Information

    All 469 features are standard; there are no options. The phase CT secondaries, control power, and analog out- put range must be specified at the time of order. The 469 differential CT inputs are field programmable for CTs with 1 A or 5 A secondaries. There are two ground CT inputs, one for the GE Power Management 50:0.025 core balance CT and one for a ground CT with a 1 A or 5 A secondary, also field programmable.
  • Page 13: Specifications

    24 V DC with Vce < 4 V DC Power: 45 VA (max), 25 VA typical 469 Sensor Supply: +24 V DC at 20 mA max. Proper operation time without supply voltage: 30 ms RTD INPUTS RTDs: 3 wire type:100 Ω Platinum (DIN.43760) PHASE CURRENT INPUTS 100 Ω...
  • Page 14 Pickup Accuracy: as per Phase Current Inputs Timing Accuracy: ±0.5 s or ±0.5% of total time Timing Accuracy: ±100 ms or ±2% of total time Elements: Trip and Alarm Elements: Trip and Alarm 469 Motor Management Relay GE Power Management...
  • Page 15 1 to 250°C in steps of 1 Elements: Trip Pickup Hysteresis:2°C Time Delay: LOAD SHED Elements: Trip and Alarm Configurable: Assignable to Digital Inputs1 to 4 Timing Accuracy: 100 ms max. Elements: Trip GE Power Management 469 Motor Management Relay...
  • Page 16 Trip and Alarm Range: 0 to 2000000.000 MW·hours. Timing Accuracy: ±0.5% Update Rate: 5 seconds METERED REACTIVE POWER CONSUMPTION Description: Continuous total of reactive power consumption. Range: 0 to 2000000.000 Mvar·hours Timing Accuracy: ±0.5% 469 Motor Management Relay GE Power Management...
  • Page 17 Pollution Degree: 2 PACKAGING 12” × 11” × 10” (W × H × D) Shipping Box: It is recommended that the 469 be powered up 30.5cm × 27.9cm × 25.4cm at least once per year to prevent deterioration NOTE of electrolytic capacitors in the power supply.
  • Page 19: Installation

    2 INSTALLATION 2.1 MECHANICAL 2.1.1 DESCRIPTION The 469 is packaged in the standard GE Power Management SR series arrangement, which consists of a dra- wout unit and a companion fixed case. The case provides mechanical protection to the unit and is used to make permanent connections to all external equipment.
  • Page 20: Product Identification

    2.1.2 PRODUCT IDENTIFICATION Each 469 unit and case are equipped with a permanent label. This label is installed on the left side (when fac- ing the front of the relay) of both unit and case. The case label details which units can be installed.
  • Page 21 2.1.3 INSTALLATION The 469 case, alone or adjacent to another SR series unit, can be installed in the panel of a standard 19-inch rack (see the diagram below for panel cutout dimensions). Provision must be made when mounting for the front door to swing open without interference to, or from, adjacent equipment.
  • Page 22: Unit Withdrawal And Insertion

    3. While holding the latch raised, grasp the locking handle in the center and pull firmly, rotating the handle up from the bottom of the unit until movement ceases. Figure 2–7: ROTATE HANDLE TO STOP POSITION 469 Motor Management Relay GE Power Management...
  • Page 23 5. When the unit is fully inserted, the latch will be heard to click, locking the handle in the final position. No special ventilation requirements need to be observed during the installation of the unit. The unit does not require cleaning. CAUTION GE Power Management 469 Motor Management Relay...
  • Page 24: Terminal Locations

    2.1 MECHANICAL 2 INSTALLATION 2.1.5 TERMINAL LOCATIONS Figure 2–9: TERMINAL LAYOUT 469 Motor Management Relay GE Power Management...
  • Page 25 2 INSTALLATION 2.1 MECHANICAL Table 2–1: 469 TERMINAL LIST RTD #1 HOT ASSIGNABLE SW. 03 RTD #1 COMPENSATION ASSIGNABLE SW. 04 RTD RETURN SWITCH COMMON RTD #2 COMPENSATION SWITCH +24 V DC RTD #2 HOT COMPUTER RS485 + RTD #3 HOT COMPUTER RS485 –...
  • Page 26: Electrical

    2.2 ELECTRICAL 2 INSTALLATION 2.2 ELECTRICAL 2.2.1 TYPICAL WIRING DIAGRAM Figure 2–10: TYPICAL WIRING DIAGRAM 469 Motor Management Relay GE Power Management...
  • Page 27: Typical Wiring

    2.2 ELECTRICAL 2.2.2 TYPICAL WIRING A broad range of 469 applications are available. Although it is not possible to present typical connections for all possible schemes, this section will cover the interconnections of instrument transformer inputs, other inputs, outputs, communications, and grounding. See Figure 2–9: TERMINAL LAYOUT on page 2–6 and Table 2–1: 469 TERMINAL LIST on page 2–7 for terminal arrangement.
  • Page 28: Phase Current Inputs

    If the unit is withdrawn, each phase CT circuit is shorted by auto- matic mechanisms on the 469 case. The phase CTs should be chosen so the FLA is no less than 50% of the rated phase CT primary.
  • Page 29 2.2 ELECTRICAL The 469 measures up to 5 A secondary current if the 1 A / 5 A tap is used. Since the conversion range is rela- tively small, the 1 A or 5 A option is field programmable. Proper selection of this setpoint ensures proper read- ing of primary ground current.
  • Page 30: Differential Current Inputs

    469 case if the unit is withdrawn. The maximum differential CT primary current is 5000 A. The 469 measures up to 5 A secondary current for the differential CT inputs. Since the conversion range is rel- atively small, the 1 A or 5 A option is field programmable. Proper selection of this setpoint ensures proper read- ing of primary phase differential current.
  • Page 31: Voltage Inputs

    2.2 ELECTRICAL 2.2.7 VOLTAGE INPUTS The 469 has three channels for AC voltage inputs, each with an isolating transformer. There are no internal fuses or ground connections on the voltage inputs. The maximum VT ratio is 150.00:1. The two VT connec- tions are open delta (see Figure 2–10: TYPICAL WIRING DIAGRAM on page 2–8) or wye (see below).
  • Page 32: Analog Inputs

    2.2.9 ANALOG INPUTS The 469 provides terminals for four 0 to 1mA, 0 to 20mA, or 4 to 20mA current input signals (field programma- ble). This current signal can be used to monitor external quantities such as vibration, pressure, or flow. The four inputs share one common return.
  • Page 33: Rtd Sensor Connections

    DESCRIPTION The 469 monitors up to 12 RTD inputs for Stator, Bearing, Ambient, or Other temperature monitoring. The type of each RTD is field programmable as 100 Ω Platinum (DIN 43760), 100 Ω Nickel, 120 Ω Nickel, or 10 Ω Cop- per.
  • Page 34: Reduced Rtd Lead Number Application

    1. There will be an error in temperature readings due to lead and connection resistances. This technique is NOT recommended for 10 Ω Copper RTDs. 2. If the RTD Return lead to the 469 or any of the jumpers break, all RTDs from the point of the break will read open.
  • Page 35: Two Wire Rtd Lead Compensation

    GROUNDING OF RTDs Grounding of one lead of the RTDs is done at either the 469 or at the motor. Grounding should not be done in both places as it could cause a circulating current to flow. Only RTD Return leads may be grounded.
  • Page 36: Output Relays

    This will provide failsafe operation of the motor; that is, the motor will be tripped off line in the event that the 469 is not protecting it. If however, the process is critical, annun- ciation of such a failure will allow the operator or the operation computer to either continue, or do a sequenced shutdown.
  • Page 37: Drawout Indicator

    2.2.13 DRAWOUT INDICATOR The Drawout Indicator is simply a jumper from terminals E12 to F12. When the 469 is withdrawn from the case, terminals E12 and F12 are open. This may be useful for differentiating between loss of control power as indi- cated by the R6 SERVICE relay and withdrawal of the unit.
  • Page 38: Rs485 Communications Ports

    The last device at each end of the daisy chain should be terminated with a 120 Ω ¼-watt resistor in series with a 1 nF capacitor across the ‘+’ and ‘–’ terminals. Observing these guidelines provides a reliable communication system immune to system transients. 469 Motor Management Relay 469 Motor Management Relay 469 Motor Management Relay Figure 2–23: RS485 COMMUNICATIONS INTERFACE...
  • Page 39: Typical 2 Speed Motor Wiring

    2 INSTALLATION 2.2 ELECTRICAL 2.2.15 TYPICAL 2 SPEED MOTOR WIRING GE Power Management 469 Motor Management Relay 2-21...
  • Page 40: Dielectric Strength Testing

    It may be required to test a complete motor starter for dielectric strength (“flash” or “hipot”) with the 469 installed. The 469 is rated for 2000 V DC isolation between relay contacts, CT inputs, VT inputs, trip coil super- vision, and the safety ground terminal G12. Some precautions are required to prevent damage to the 469 dur- ing these tests.
  • Page 41: Operation

    R5 BLOCK START R6 SERVICE LOCKOUT GROUND PICKUP RESET HOT RTD POSSIBLE RESET MESSAGE LOSS OF LOAD NEXT PROGRAM PORT SETPOINT MESSAGE ACTUAL ESCAPE VALUE HELP ENTER Motor Management Relay® 806766A5.CDR Figure 3–1: 469 FACEPLATE GE Power Management 469 Motor Management Relay...
  • Page 42: Display

    469 STATUS LED INDICATORS • 469 IN SERVICE: Control power is applied, all monitored I/O and internal systems are OK, the 469 has been programmed, and the 469 is in protection mode, not simulation mode. When in simulation or testing mode, the LED indicator will flash.
  • Page 43: Motor Status Led Indicators

    469PC software. Local interrogation of setpoints and actual values is also possible. New firmware may also be downloaded to the 469 flash memory through this port. Upgrading of the relay firmware does not require a hardware EPROM change.
  • Page 44: Keypad

    3. Repeat step 2 for the remaining characters: h,e,c,k, ,F,l,u,i,d, ,L,e,v,e,l,s. 4. Press ENTER to store the text message. 3.1.7 ENTERING +/– SIGNS The 469 does not have ‘+’ or ‘–’ keys. Negative numbers may be entered in one of two manners. VALUE • Immediately pressing the VALUE keys causes the setpoint to scroll through its range includ- ing any negative numbers.
  • Page 45: Setpoint Entry

    The following procedure may be used to access and alter setpoints. This specific example refers to entering a valid passcode to allow access to setpoints if the passcode was "469". SETPOINT 1. The 469 programming is broken down into pages by logical groups. Press to cycle through the set- MESSAGE point pages until the desired page appears on the screen.
  • Page 47: Trips/Alarms/Blocks Defined

    BLOCK START An 469 Block Start is a feature that prevents or inhibits the start of the motor based on some logic or algorithm. An 469 Block Start feature is always assigned to the Block Start relay. In addition to the Trip relay(s), a trip will always operate Block Start relay.
  • Page 48: Relay Assignment Practices

    There are six output relays. Five of the relays are always non-failsafe, the other (Service) is failsafe and dedi- cated to enunciate internal 469 faults (these faults include Setpoint Corruption, failed hardware components, loss of control power, etc.). One of the output relays is dedicated as the Block Start relay; it is dedicated to fea- tures that are intended to block motor starting.
  • Page 49: Setpoint Message Map

    S ANALOG IN 3-4 DIFF2 † ASSIGNABLE INPUT 4 dedicated as two-speed monitor if the Two-Speed Motor feature is used. The two-speed motor protection is enabled in S2 SYSTEM SETUP \ CURRENT SENSING. GE Power Management 469 Motor Management Relay...
  • Page 50: S1 469 Setup

    4.2 S1 469 SETUP 4 SETPOINT PROGRAMMING 4.2 S1 469 SETUP 4.2.1 PASSCODE S PASSCODE ð Range: 1 to 8 numeric digits. This message is seen only if the ENTER PASSCODE FOR ENTER passcode is not 0 and setpoint access is restricted.
  • Page 51: Preferences

    4 SETPOINT PROGRAMMING 4.2 S1 469 SETUP 4.2.2 PREFERENCES S PREFERENCES ð Range: 0.5 to 10.0 sec., step: 1 DEFAULT MESSAGE ENTER S [ENTER] for more CYCLE TIME: 2.0 s ESCAPE Range: 10 to 900 sec., step: 1 DEFAULT MESSAGE...
  • Page 52: Serial Ports

    If the RS485 serial communication link is used, then all the relays can keep synchronized time. A new clock time is pre-loaded into the 469 memory via the RS485 port by a remote computer to each relay connected on the communications channel. After the computer broadcasts (address 0) a "set clock" command, all relays in the system begin timing at the same instant.
  • Page 53: Default Messages

    Management Relay MESSAGE After a period of inactivity, the 469 displays default messages. Between 1 to 20 default messages can be selected. Multiple default messages automatically scan in sequence at a rate determined by S1 469 SETUP \PREFERENCES\DEFAULT MESSAGE CYCLE TIME. Any actual value can be selected for default display; in addition, up to five user programmable messages can be created and displayed (Message Scratchpad).
  • Page 54: Message Scratchpad

    4.2 S1 469 SETUP 4 SETPOINT PROGRAMMING 4.2.6 MESSAGE SCRATCHPAD S MESSAGE SCRATCHPAD ð Range: 40 character alphanumeric TEXT 1 ENTER S [ENTER] for more ESCAPE Range: 40 character alphanumeric TEXT 2 ESCAPE MESSAGE Range: 40 character alphanumeric TEXT 3...
  • Page 55: Clear Data

    4 SETPOINT PROGRAMMING 4.2 S1 469 SETUP 4.2.7 CLEAR DATA S CLEAR DATA ð Range: No, Yes CLEAR LAST TRIP ENTER S [ENTER] for more DATA: No ESCAPE Range: No, Yes RESET MWh and Mvarh ESCAPE METERS: No MESSAGE Range: No, Yes...
  • Page 56: Installation

    ESCAPE INFORMATION: No MESSAGE These commands clear various informative and historical data when the 469 is first applied on a new installa- tion. RESET MOTOR INFORMATION: Counters for number of motor starts and number of emergency restarts can be viewed in actual values. The 469 also learns various motor characteristics through motor operation. These learned parameters include acceleration time, starting current, and starting thermal capacity.
  • Page 57: S2 System Setup

    As a safeguard, PHASE CT PRIMARY and MOTOR FULL LOAD AMPS are defaulted to "Not Programmed" when shipped from the factory. A block start indicates that the 469 was never programmed. Once PHASE CT PRIMARY and MOTOR FULL LOAD AMPS are entered, the alarm resets itself. The phase CT should be chosen so the FLA is no less than 50% of the rated phase CT primary.
  • Page 58: Examples

    EXAMPLES 1. Given the following specifications: Motor Nameplate FLA: 87 A, Low Resistance Grounded, Maximum Fault: 400 A, 469 purchased with 5 A phase CT Secondary, Ground Fault Detection to be Residual Make the following settings: PHASE CT PRIMARY: "100"...
  • Page 59: Power System

    The 469 may be used on variable frequency drives when the NOMINAL SYSTEM FREQUENCY is set to "Variable". All of the elements function in the same manner with the following exceptions: the ratio of negative to positive sequence current is calculated from 0 to 30%, not 40%, and the voltage and power elements will work properly if the voltage waveform is approximately sinusoidal.
  • Page 60: Reduced Voltage

    START TIMER: 200 s MESSAGE The 469 can control the transition of a reduced voltage starter from reduced to full voltage. That transition may be based on "Current Only", "Current and Timer", or "Current or Timer" (whichever comes first). When the 469 mea- sures the transition of no motor current to some value of motor current, a 'Start' is assumed to be occurring (typically current will rise quickly to a value in excess of FLA, e.g.
  • Page 61 ‘b’ contacts from the reduced voltage contactor and the full voltage contactor. Once transition NOTE is initiated, the 469 assumes the motor is still running for at least 2 seconds. This prevents the 469 from recognizing an additional start if motor current goes to zero during an open transi- tion.
  • Page 62: S3 Digital Inputs

    4.4.3 TEST SWITCH Once the 469 is in service, it may be tested from time to time as part of a regular maintenance schedule. The relay will have accumulated statistical information relating historically to starter and motor operation. This infor-...
  • Page 63: Starter Status

    Closure of the contact signifies that the motor is in Speed 2 or High Speed. If the input is open, it signifies that the motor is in Speed 1. This allows the 469 to determine which setpoints should be active at any given point in time.
  • Page 64: Digital Input Function: Remote Alarm

    Multiple sources may be used to trigger a remote trip by paralleling inputs. REMOTE PUSH-BUTTO N 469 Digital Input Dry contact from other device Figure 4–6: REMOTE TRIP FROM MULTIPLE SOURCES 4-18 469 Motor Management Relay GE Power Management...
  • Page 65: Digital Input Function: Speed Switch Trip

    After the block delay has expired, the digital input will be monitored. If a closure occurs, after the specified delay, an alarm will occur. GE Power Management 469 Motor Management Relay 4-19...
  • Page 66: Digital Input Function: Pressure Switch Trip

    When the motor is stopped or running, the digital input will be monitored. If a closure occurs, after the specified delay, a trip will occur. 4-20 469 Motor Management Relay GE Power Management...
  • Page 67: Digital Input Function: Digital Counter

    An alarm may be configured when a certain count is reached. The counter value may be viewed in A4 MAINTENANCE\GENERAL COUNTERS\DIGITAL COUNTER. To initialize the counter, program the counter value here and then change S1 469 SETUP\CLEAR DATA\PRESET DIGITAL COUNTER to "Yes".
  • Page 68: Function

    +24 V from the input switch power supply. The NPN transistor output could be taken to one of the assignable switch inputs configured as a tachometer. 4-22 469 Motor Management Relay GE Power Management...
  • Page 69: Digital Input Function: General Switch A-D

    4.4.22 DIGITAL INPUT FUNCTION: SIMULATE PRE-FAULT…FAULT This setting allows the user to start Simulate Pre-Fault to Fault mode as programmed in S13 via a switch input. This is typically used for relay or system testing. GE Power Management 469 Motor Management Relay 4-23...
  • Page 70: S4 Output Relays

    Shorting bars in the drawout case ensure that when the 469 is drawn out, no trip or alarm occurs. The R6 Service output will how- ever indicate that the 469 has been drawn out.
  • Page 71: Force Output Relay

    The FORCE OUTPUT RELAY option is NOT allowed when the selected relay output is already active due to trip or alarm condition, when the 469 is in start block condition, or when the 469 is not in service. IMPORTANT NOTE: •...
  • Page 72: S5 Thermal Model

    The motor manufacturer should provide a safe stall time or thermal limit curves for any motor they sell. To pro- gram the 469 for maximum protection, it is necessary to ask for these items when the motor is out for bid.
  • Page 73 CURVES AT 100%, 90%, AND 80%VOLTAGE, REPECTIVELY E,F, AND G ARE THE SAFE STALL THERMAL LIMIT TIMES AT 100%, 90%, AND 80%VOLTAGE, REPECTIVELY % CURRENT 806827A1.CDR Figure 4–7: TYPICAL TIME-CURRENT AND THERMAL LIMIT CURVES (ANSI/IEEE C37.96) GE Power Management 469 Motor Management Relay 4-27...
  • Page 74: Thermal Model

    ALARM EVENTS: Off MESSAGE The primary protective function of the 469 is the thermal model. It consists of five key elements: the overload curve and overload pickup level, the unbalance biasing of the motor current while the motor is running, the motor cooling time constants, and the biasing of the thermal model based on Hot/Cold motor information and measured stator temperature.
  • Page 75: Overload Curve Setup

    4.00 x FLA: 23.3 s MESSAGE Range: 0.5 to 99999.9 s; Step 1 TIME TO TRIP AT ESCAPE Cannot be altered if Standard Curve Style is selected. 4.25 x FLA: 20.5 s MESSAGE GE Power Management 469 Motor Management Relay 4-29...
  • Page 76 100% Vline: 10.0 s MESSAGE Range: 2.00 to Istall @ min. Vline; Step: 0.01 ACCEL. INTERSECT @ ESCAPE Message seen only if Standard Curve Style is selected. 100% Vline: 5.00 x FLA MESSAGE 4-30 469 Motor Management Relay GE Power Management...
  • Page 77: Function

    If the motor starting times are well within the safe stall times, it is recommended that the 469 Standard Over- load Curve be used. The standard overload curves are a series of 15 curves with a common curve shape based on typical motor thermal limit curves (see Figure 4–8: 469 STANDARD OVERLOAD CURVES and Table...
  • Page 78 4.6 S5 THERMAL MODEL 4 SETPOINT PROGRAMMING 100000 10000 1000 1.00 0.10 1.00 1000 MULTIPLE OF FULL LOAD AMPS 806804A5.CDR Figure 4–8: 469 STANDARD OVERLOAD CURVES 4-32 469 Motor Management Relay GE Power Management...
  • Page 79 4 SETPOINT PROGRAMMING 4.6 S5 THERMAL MODEL Table 4–1: 469 STANDARD OVERLOAD CURVE MULTIPLIERS PICKUP STANDARD CURVE MULTIPLIERS LEVEL × 1 × 2 × 3 × 4 × 5 × 6 × 7 × 8 × 9 × 10 × 11 ×...
  • Page 80 4 SETPOINT PROGRAMMING Figure 4–9: CUSTOM CURVE EXAMPLE During the interval of discontinuity, the longer of the two trip times is used to reduce the chance of nuisance tripping during motor starts. NOTE 4-34 469 Motor Management Relay GE Power Management...
  • Page 81 The relay that is protecting the motor must be able to distinguish between a locked rotor condition, an accelerating condition and a running condition. The 469 Voltage Depen- dent Overload Curve feature is tailored to protect these types of motors. Voltage is continually monitored dur- ing motor starting and the acceleration thermal limit curve is adjusted accordingly.
  • Page 82 4- Locked Rotor Thermal Limit 5- Motor Acceleration Curve @ 80% V 6- Motor Acceleration Curve @ 100%V MULTIPLES OF FULL LOAD AMPS 806821A3.CDR Figure 4–10: THERMAL LIMITS FOR HIGH INERTIAL LOAD 4-36 469 Motor Management Relay GE Power Management...
  • Page 83: Custom Overload Curve

    GE Power Management HIGH INERTIA LOAD OVERLOAD CURVES 8800 HP, 13.2 kV, REACTOR COOLANT PUMP 1000 469 Custom Curve MULTIPLES OF FULL LOAD AMPS 806822A3.CDR 806822A3.CDR Figure 4–11: VOLTAGE DEPENDENT OVERLOAD (CUSTOM CURVE) GE Power Management 469 Motor Management Relay 4-37...
  • Page 84 HIGH INERTIA LOAD OVERLOAD CURVES 8800 HP, 13.2 kV, REACTOR COOLANT PUMP 1000 Acceleration intersect @ 80%V Acceleration Intersect @ 100%V MULTIPLES OF FULL LOAD AMPS 806823A3.CDR Figure 4–12: VOLTAGE DEPENDENT OVERLOAD (ACCELERATION CURVES) 4-38 469 Motor Management Relay GE Power Management...
  • Page 85 The 469 takes the information provided and create protection curves for any voltage between the minimum and 100%. For values above the voltage in question, the 469 extrapolates the safe stall protection curve to 110% voltage. This current level is calculated by taking the locked rotor current @ 100% voltage and multiply- ing by 1.10.
  • Page 86 The following two figures illustrate the resultant overload protection curves for 80% and 100% line voltage, respectively. For voltages in between, the 469 will shift the acceleration curve linearly and constantly based on measured line voltage during a motor start.
  • Page 87 GE Power Management GE Power Management HIGH INERTIA LOAD OVERLOAD CURVES 8800 HP, 13.2 kV, REACTOR COOLANT PUMP 1000 MULTIPLES OF FULL LOAD AMPS 806826A3.CDR Figure 4–15: VOLTAGE DEPENDENT OVERLOAD PROTECTION AT 100% V GE Power Management 469 Motor Management Relay 4-41...
  • Page 88: Unbalance Bias

    The 469 measures the ratio of negative to positive-sequence current. The thermal model may be biased to reflect the additional heating that is caused by negative sequence current when the motor is running. This bias- ing is accomplished by creating an equivalent motor heating current rather than simply using average current ).
  • Page 89: Motor Cooling

    Motor Stopped after Overload Trip Motor Stopped after running Rated Load TCused_end= 0% TCused_end= 0% Time in Minutes Time in Minutes Thermal Model Cooling, Motor Stopped Thermal Model Cooling, Motor Tripped Figure 4–17: THERMAL MODEL COOLING GE Power Management 469 Motor Management Relay 4-43...
  • Page 90: Hot/Cold Curve Ratio

    If the motor stator has embedded RTDs, the 469 RTD bias feature should be used to correct the thermal model. The RTD bias feature is a two-part curve, constructed using 3 points. If the maximum stator RTD temperature is below the RTD BIAS MINIMUM setpoint (typically 40°C), no biasing occurs.
  • Page 91 Presumably, the motor would trip on stator RTD temperature at that time. RTD Bias Maximum Hot/Cold = 0.85 Rated Temperature=130 C Insulation Rating=155 C RTD Bias Center Point RTD Bias Minimum Maximum Stator RTD Temperature Figure 4–18: RTD BIAS CURVE GE Power Management 469 Motor Management Relay 4-45...
  • Page 92: S6 Current Elements

    The overreach filter removes the DC component from the asymmetrical current present at the moment a fault occurs. This results in no overreach whatsoever, however, the response time slows slightly (10 to 15 ms) but times still remain within specifications. 4-46 469 Motor Management Relay GE Power Management...
  • Page 93: Overload Alarm

    The MECHANICAL JAM PICKUP level should be set higher than motor loading during normal operation, but lower than the motor stall level. Normally the delay is set to the minimum time delay or set so that no nuisance trips occur due to momentary load fluctuations. GE Power Management 469 Motor Management Relay 4-47...
  • Page 94: Undercurrent

    BLOCK UNDERCURRENT FROM START setpoint should be disabled (programmed as 0). • the UNDERCURRENT ALARM DELAY / UNDERCURRENT TRIP DELAY is typically set as quick as possible, i.e. 1 s. 4-48 469 Motor Management Relay GE Power Management...
  • Page 95: Current Unbalance

    ESCAPE TRIP DELAY: 1 s MESSAGE a) FUNCTION 469 unbalance is defined as the ratio of negative-sequence to positive-sequence current, I , if the motor is operating at a load ( I ) greater than FLA. If the motor I is less than FLA, unbalance is defined as I ×...
  • Page 96: Ground Fault

    GROUND FAULT TRIP BACKUP DELAY. It is intended that this second trip be assigned to R2 or R3, which would be dedicated as an upstream breaker trip relay. The GROUND FAULT TRIP BACKUP DELAY must be set to a time longer than the breaker clearing time. 4-50 469 Motor Management Relay GE Power Management...
  • Page 97 This momentary DC component will cause each of the phase CTs to react differently and the net current into the ground input of the 469 will not be negligible. A 20 ms block of the ground fault elements when the motor starts enables the 469 to ride through this momentary ground current signal.
  • Page 98: Phase Differential

    STARTING DIFF. TRIP DELAY may have to be extended to ride through the problem period during start. The running differential delay can then be fine tuned to an application such that it responds very fast to sensitive (low) differential current levels. 4-52 469 Motor Management Relay GE Power Management...
  • Page 99: S7 Motor Starting

    Some motor softstarters may allow current to ramp up slowly while others may limit current to less than FLA throughout the start. Since the 469 is a generic relay for protection of all motors, it cannot differentiate between a motor that has a slow ramp up time and one that has completed a start and NOTE gone into an overload condition.
  • Page 100: Start Inhibit

    If the COOL TIME CONSTANT STOPPED setpoint is programmed for 30 minutes, the lockout time will be equal to: t – τ ⁄ × used used_start ⁄ t – 30 ×   × ----- - –   9.3 minutes 4-54 469 Motor Management Relay GE Power Management...
  • Page 101: Jogging Block

    STARTS / HOUR A motor start is assumed to be occurring when the 469 measures the transition of no motor current to some value of motor current. At this point, one of the Starts/Hour timers is loaded with 60 minutes. Even unsuccess- ful start attempts will be logged as starts for this feature.
  • Page 102: Restart Block

    The motor has now become a generator and applying supply voltage out of phase may result in catastrophic failure. The Restart Block feature is strictly a timer. The 469 does not sense rotor rotation. NOTE...
  • Page 103: S8 Rtd Temperature

    168.47 280.77 233.97 16.00 172.46 291.96 243.30 16.39 175.84 303.46 252.88 16.78 179.51 315.31 262.76 17.17 183.17 327.54 272.94 17.56 186.82 340.14 283.45 17.95 190.45 353.14 294.28 18.34 194.08 366.53 305.44 18.73 GE Power Management 469 Motor Management Relay 4-57...
  • Page 104: Rtds 1 To 6

    RTD being checked before a trip will be issued. If the RTD is chosen to vote with itself, the voting feature is disabled. Each RTD name may be changed if desired. 4-58 469 Motor Management Relay GE Power Management...
  • Page 105: Rtds 7 To 10

    RTD must also exceed the trip temperature of the RTD being checked before a trip will be issued. If the RTD is chosen to vote with itself, the voting feature is disabled. Each RTD name may be changed if desired. GE Power Management 469 Motor Management Relay 4-59...
  • Page 106: Rtd 11

    If enabled, a second RTD must also exceed the trip temperature of the RTD being checked before a trip will be issued. If the RTD is chosen to vote with itself, the voting feature is disabled. The RTD name may be changed if desired. 4-60 469 Motor Management Relay GE Power Management...
  • Page 107: Rtd 12

    If enabled, a second RTD must also exceed the trip temperature of the RTD being checked before a trip will be issued. If the RTD is chosen to vote with itself, the voting feature is disabled. The RTD name may be changed if desired. GE Power Management 469 Motor Management Relay 4-61...
  • Page 108: Open Rtd Sensor

    MESSAGE The 469 has an Open RTD Sensor Alarm. This alarm will look at all RTDs that have either an alarm or trip pro- grammed and determine if an RTD connection has been broken. Any RTDs that do not have a trip or alarm associated with them will be ignored for this feature.
  • Page 109: S9 Voltage Elements

    This may be especially critical for a synchronous motor. This feature may be used in with a time delay to provide protection for undervoltage conditions before and during starting. GE Power Management 469 Motor Management Relay 4-63...
  • Page 110: Overvoltage

    MESSAGE The 469 can detect the phase rotation of the three phase voltage. If the Phase Reversal feature is turned on when all 3 phase voltages are greater than 50% motor nameplate voltage, and the phase rotation of the three phase voltages is not the same as the setpoint, a trip and block start will occur in 500 to 700 ms.
  • Page 111: Frequency

    This feature may be useful for load shedding applications on large motors. It could also be used to load shed an entire feeder if the trip was assigned to an upstream breaker. GE Power Management 469 Motor Management Relay 4-65...
  • Page 112: S10 Power Elements

    4.11 S10 POWER ELEMENTS 4.11.1 POWER MEASUREMENT CONVENTIONS By convention, an induction motor consumes Watts and vars. This condition is displayed on the 469 as +Watts and +vars. A synchronous motor can consume Watts and vars or consume Watts and generate vars. These conditions are displayed on the 469 as +Watts, +vars, and +Watts, –vars respectively (see the figure below).
  • Page 113: Power Factor

    MESSAGE If the 469 is applied on a synchronous motor, it is desirable not to trip or alarm on power factor until the field has been applied. Therefore, this feature can be blocked until the motor comes up to speed and the field is applied.
  • Page 114: Reactive Power

    MESSAGE If the 469 is applied on a synchronous motor, it is desirable not to trip or alarm on kvar until the field has been applied. Therefore, this feature can be blocked until the motor comes up to speed and the field is applied. From that point forward, the kvar trip and alarm elements will be active.
  • Page 115: Underpower

    Power is a more accurate representation of loading and may be used for more sensitive detection of load loss or pump cavitation. This may be especially useful for detecting process related problems. GE Power Management 469 Motor Management Relay 4-69...
  • Page 116: Reverse Power

    The minimum magnitude of power measurement is determined by the phase CT minimum of 5% rated CT primary. If the level for reverse power is set below that level, a trip or alarm will only occur once the phase current exceeds the 5% cutoff. NOTE 4-70 469 Motor Management Relay GE Power Management...
  • Page 117: Torque Setup

    Detection of a motor overtorque condition, usually done to protect devices driven by the motor, can be set up here. The assigned relay activates when the torque measured exceeds the specified level for the specified time duration. GE Power Management 469 Motor Management Relay 4-71...
  • Page 118: S11 Monitoring

    If the STARTER FAILURE ALARM is set to "Latched" or "Unlatched", then the Starter Status input and motor current are monitored when the 469 initiates a trip. If the starter status contacts do not change state or motor current does not drop to zero after the programmed time delay, an alarm occurs. The time delay should be slightly longer than the breaker or contactor operating time.
  • Page 119 VALUE OF RESISTOR 'R' SUPPLY OHMS WATTS 48 VDC 10 K TRIP 125 VDC 25 K COIL 250 VDC 50 K TRIP COIL OPEN/CLOSED SUPERVISION "52 Open/Closed" Figure 4–20: TRIP COIL SUPERVISION GE Power Management 469 Motor Management Relay 4-73...
  • Page 120: Current, Kw, Kvar, Kva Demand

    Alarm & Auxiliary3, Auxiliary2, Aux2 & Aux3, Auxiliary3 Alarm MESSAGE Range: 1 to 50000 kVA, step: 1 kVA DEMAND ESCAPE LIMIT: 100 kVA MESSAGE Range: On, Off kVA DEMAND ESCAPE ALARM EVENTS: Off MESSAGE 4-74 469 Motor Management Relay GE Power Management...
  • Page 121 4 SETPOINT PROGRAMMING 4.12 S11 MONITORING The 469 measures motor demand for several parameters (current, kW, kvar, and kVA). These values may be of interest for energy management programs where processes may be altered or scheduled to reduce overall demand on a feeder.
  • Page 122: Pulse Output

    1 second. This feature should be programmed such that no more than one pulse per second will be required or the pulsing will lag behind the interval activation. NOTE 4-76 469 Motor Management Relay GE Power Management...
  • Page 123: S12 Analog I/O

    MESSAGE The 469 has four analog output channels (4 to 20 mA or 0 to 1 mA as ordered). Each channel may be individ- ually configured to represent a number of different measured parameters as shown in the table below. The minimum value programmed represents the 4 mA output.
  • Page 124: Analog Output Table

    100 to 7200 RPM 3500 3700 MWhrs 0.000 to 999999.999 MWhrs 0.001 50.000 100.000 Analog In Diff 1-2 –50000 to +50000 Analog In Diff 3-4 –50000 to +50000 Torque 0 to 999999.9 4-78 469 Motor Management Relay GE Power Management...
  • Page 125: Analog Inputs 1-4

    Units will reflect Analog Input 1 Units as entered above LEVEL: 20 Units MESSAGE Range: Over, Under ANALOG INPUT 1 TRIP ESCAPE PICKUP: Over MESSAGE Range: 0.1 to 300.0 sec., step 0.1 ANALOG INPUT 1 TRIP ESCAPE DELAY: 0.1 s MESSAGE GE Power Management 469 Motor Management Relay 4-79...
  • Page 126: Function

    Program ANALOG INPUT 1/2/3/4 BLOCK FROM START as "0" minutes. Set the alarm for a reasonable level slightly higher than the normal vibration level. Program a delay of "3 s" and a pickup value of "Over". 4-80 469 Motor Management Relay GE Power Management...
  • Page 127 For example, two motors on a dual motor drive are each protected a 469. The motors should be at the same power level (kW). Connect the analog outputs (programmed for kW) from both relays to the analog inputs of one relay.
  • Page 128: Analog In Diff 3-4

    ("3>4") or vice versa ("4>3") or as absolute difference ("3<>4"). Note that the compared analog inputs must be programmed with the same unit type prior to using this feature. 4-82 469 Motor Management Relay GE Power Management...
  • Page 129: S13 469 Testing

    If however, the 469 has been installed and will remain installed on a specific motor, it might be desirable to short the 469 Test input (C3 and C4) to prevent all of this data from being corrupted or updated.
  • Page 130: Pre-Fault Setup

    Range: 0 to 100%, step 1 PRE-FAULT ANALOG ESCAPE INPUT 4: 0% MESSAGE The values entered under Pre-Fault Values will be substituted for the measured values in the 469 when the simulation mode is "Simulate Pre-Fault". 4-84 469 Motor Management Relay GE Power Management...
  • Page 131: Fault Setup

    Range: 0 to 100%, step 1 FAULT ANALOG ESCAPE INPUT 4: 0% MESSAGE The values entered under Fault Values will be substituted for the measured values in the 469 when the simula- tion mode is "Simulate Fault". GE Power Management 469 Motor Management Relay 4-85...
  • Page 132: Test Output Relays

    FORCE ANALOG OUTPUTS FUNCTION is automatically disabled and all analog outputs revert back to their normal state. Any time the analog outputs are forced, the 469 In Service LED will flash, indicating that the 469 is not in pro- tection mode.
  • Page 133: Comm Port Monitor

    Rx1 and Rx2 buffers with ‘//’ act- ing as a character break between messages. If the 469 transmits a message, it will appear in the Tx1 and Tx2 buffers.
  • Page 134: S14 Two-Speed Motor

    D22 and D23 are monitored for a contact closure. Closure of the contact signifies that the motor is in Speed 2. If the input is open, it signifies that the motor is in Speed 1. This allows the 469 to determine which setpoints should be active at any given point in time.
  • Page 135 @ MIN Vline: 3.80 x FLA MESSAGE Range: 2.00 to 15.00 x FLA; Step: 0.01 SPEED2 ISTALL @ 100% ESCAPE Message seen only if Voltage Dependent Curve Style is selected Vline: 6.00 x FLA MESSAGE GE Power Management 469 Motor Management Relay 4-89...
  • Page 136: Speed2 Undercurrent

    The addition of a second Undercurrent trip or alarm level may be useful as it will indicate if the wrong setpoints are being used for the wrong speed i.e. normal running current for Speed 2 may be undercurrent for Speed 1. 4-90 469 Motor Management Relay GE Power Management...
  • Page 137: Speed2 Acceleration

    Speed 2 from a stopped condition. The other is an acceleration timer for the transition from Speed 1 to Speed 2. Also, while the motor is running, the 469 will ignore Mechanical Jam protection during the acceleration from Speed 1 to Speed 2 until the motor current has dropped below Speed 2 FLA × Overload Pickup value, or the Speed 1-2 acceleration time has expired.
  • Page 139: Actual Values

    Actual value messages are organized into logical groups, or pages, for easy reference. All actual value mes- sages are illustrated and described in blocks throughout this chapter. All values shown in these message illus- trations assume that no inputs (besides control power) are connected to the 469. Table 5–1: ACTUAL VALUES MESSAGES...
  • Page 140: A1 Status

    These messages describe the motor status at any given point in time. If the motor has been tripped and the 469 has not yet been reset, the MOTOR STATUS value will be "Tripped". The MOTOR THERMAL CAPACITY USED reflects an integrated value of both the Stator and Rotor Thermal Capacity Used. The values for ESTIMATED TRIP TIME ON OVERLOAD appear whenever the 469 picks up on the overload curve.
  • Page 141: Last Trip Data

    Not seen if VT Connection is programmed as Wye Vcn: 0 V PreTrip MESSAGE Range: 0.00, 20.00 to 120.00 Hz PRETRIP SYSTEM ESCAPE Not seen if VT Connection is programmed as None FREQUENCY: 0.00 Hz MESSAGE GE Power Management 469 Motor Management Relay...
  • Page 142 PreTrip: 0 Units MESSAGE Immediately prior to issuing a trip, the 469 takes a snapshot of motor parameters and stores them as pre-trip values that allow for troubleshooting after the trip occurs. The CAUSE OF LAST TRIP message is updated with the current trip and the screen defaults to that message.
  • Page 143: Alarm Status

    System voltage frequency value is shown here ALARM: 59.4 Hz MESSAGE Range: 0.00 to 0.99 Lead or Lag, 0.00, 1.00 POWER FACTOR ESCAPE Current Power Factor is shown here ALARM PF: 0.00 MESSAGE GE Power Management 469 Motor Management Relay...
  • Page 144 EMERGENCY RESTART: ESCAPE No Trips & No Blocks Trip Still Present MESSAGE If the 469 chassis is only partially engaged with the case, this ALARM, 469 NOT ESCAPE service alarm appears after 1 sec. Secure the chassis handle to INSERTED PROPERLY...
  • Page 145: Start Blocks

    ESCAPE LOCKOUT: 1200 s MESSAGE Range: N/A BLOCK START ESCAPE Seen only if Phase CT Primary and Motor FLA not programmed 469 NOT PROGRAMMED MESSAGE Any active blocking functions may be viewed here. GE Power Management 469 Motor Management Relay...
  • Page 146: Digital Inputs

    Range: 01 to 12 / 01 to 31 / 1995 to 2094 DATE: 01/01/1994 ENTER S [ENTER] for more TIME: 12:00:00 ESCAPE The time and date from the 469 real time clock may be viewed here. 469 Motor Management Relay GE Power Management...
  • Page 147: A2 Metering Data

    / FLA. This derating is necessary to pre- vent nuisance alarms and trips when a motor is lightly loaded. The U/B BIASED MOTOR LOAD value shows the equivalent motor heating current caused by the unbalance k factor. GE Power Management 469 Motor Management Relay...
  • Page 148: Temperature

    The current level of the 12 RTDs is displayed here. If the RTD is not connected, the value will be "No RTD". If no RTDs are programmed in S8 RTD TEMPERATURE, the following flash message will appear when an attempt is made to enter this group of messages. THIS FEATURE NOT PROGRAMMED 5-10 469 Motor Management Relay GE Power Management...
  • Page 149: Voltage Metering

    If no digital input is configured as tachometer in S3 DIGITAL INPUTS \ ASSIGNABLE INPUT1/2/3/4, the following flash message will appear when an attempt is made to enter this group of messages. THIS FEATURE NOT PROGRAMMED GE Power Management 469 Motor Management Relay 5-11...
  • Page 150: Power Metering

    NOTE 5.3.6 TORQUE ALARM MESSAGE ð TORQUE ENTER ALARM: 0.00 ESCAPE This message appears in the Alarm Status Event Record (if programmed) and as a display message when an overtorque alarm occurs. 5-12 469 Motor Management Relay GE Power Management...
  • Page 151: Demand Metering

    The values for current and power demand are shown here. Peak Demand information can be cleared using the S1 469 SETUP \ CLEAR DATA \ CLEAR PEAK DEMAND DATA setpoint. Demand is shown only for positive real and pos- itive reactive power (+Watts and +vars).
  • Page 152: Analog Inputs

    If no analog inputs are programmed in S12 ANALOG I/O \ ANALOG INPUT 1/2/3/4, the following flash message will appear when an attempt is made to enter this group of messages. THIS FEATURE NOT PROGRAMMED 5-14 469 Motor Management Relay GE Power Management...
  • Page 153: Phasors

    Note that the phase angle for Va (Vab if delta) is always assumed to be 0° and is the reference for all angle measurements. Common problems include: Phase currents 180° from proper location (CT polarity reversed) Phase currents or voltages 120 or 240° out (CT/VT on wrong phase) GE Power Management 469 Motor Management Relay 5-15...
  • Page 154 45° = 0.7 pf lag 0° = 1.00 pf –45° = 0.7 pf lead –72.5° = 0.2 pf lead 0° 0° 0° ---- ---- ---- ---- ---- kVAR – – + (=kW) 5-16 469 Motor Management Relay GE Power Management...
  • Page 155: A3 Learned Data

    ESCAPE The 469 can learn the average motor load over a period of time. This time is specified by the S1 469 SETUP \ PREFERENCES \ AVERAGE MOTOR LOAD CALC. PERIOD setpoint (default 15 minutes). The calculation is a sliding window and is ignored during motor starting.
  • Page 156: Rtd Maximums

    MAX. TEMP .: 40°C MESSAGE The 469 will learn the maximum temperature for each RTD. This information can be cleared using the S1 469 SETUP \ CLEAR DATA \ CLEAR RTD MAXIMUMS setpoint. If no RTDs are programmed in S8 RTD TEMPERATURE, the following flash message will appear when an attempt is made to enter this group of messages.
  • Page 157: Analog In Min/Max

    The 469 will learn the minimum and maximum values of the analog inputs since they were last cleared. This information can be cleared with the S1 469 SETUP \ CLEAR DATA \ CLEAR ANALOG I/P MIN/MAX setpoint. When the data is cleared, the present value of each analog input will be loaded as a starting point for both minimum and maximum.
  • Page 158: A4 Maintenance

    ESCAPE TRIPS: 0 MESSAGE Range: 0 to 50000 UNDERVOLTAGE ESCAPE TRIPS: 0 MESSAGE Range: 0 to 50000 OVERVOLTAGE ESCAPE TRIPS: 0 MESSAGE PHASE REVERSAL Range: 0 to 50000 ESCAPE TRIPS: 0 MESSAGE 5-20 469 Motor Management Relay GE Power Management...
  • Page 159 MESSAGE A breakdown of number of trips by type is displayed here. When the Total reaches 50000, all counters reset. This information can be cleared using the S1 469 SETUP\CLEAR DATA\CLEAR TRIP COUNTERS setpoint. GE Power Management 469 Motor Management Relay...
  • Page 160: General Counters

    One of the 469 timers accumulates the total running time for the Motor. This may be useful for scheduling rou- tine maintenance. When this timer reaches 100000, it will reset to 0. This timer can be cleared using the S1 469 SETUP \ INSTALLATION \ RESET MOTOR INFORMATION setpoint.
  • Page 161: A5 Event Recorder

    Range: 0.01 to 0.99 Lead or Lag, 0.00, 1.00 POWER FACTOR ESCAPE Seen only if VT Connection programmed as None EVENT01: 0.00 MESSAGE TORQUE Range: 0 to 999999.9 ESCAPE Seen only if Torque Metering is Enabled EVENT01: 0.0 Nm MESSAGE GE Power Management 469 Motor Management Relay 5-23...
  • Page 162 The latter event could occur if the block start contacts were shorted out to bypass the 469 and start the motor. EVENT 01 is the most recent event and EVENT 40 is the oldest event. Each new event bumps the other event records up one until EVENT 40 is reached.
  • Page 163 Current Demand Alarm Power Factor Trip kW Demand Alarm Underpower Trip kvar Demand Alarm Analog I/P 1 to 4 Trip kVA Demand Alarm Single Phasing (Unbalanced) Analog I/P 1 to 4 Alarm Overtorque GE Power Management 469 Motor Management Relay 5-25...
  • Page 164: A6 Product Info

    MESSAGE All of the 469 model information may be viewed here when the unit is powered up. In the event of a product software upgrade or service question, the information shown here should be jotted down prior to any inquiry.
  • Page 165: Diagnostics

    When an overload trip occurs, an RTD alarm may also occur as a result of the overload and a lockout time associated with the trip. The 469 automatically defaults to the A1 ACTUAL VALUES \ LAST TRIP DATA \ CAUSE OF LAST TRIP actual value message and the Message LED flashes.
  • Page 166: Flash Messages

    • ROUNDED SETPOINT HAS BEEN STORED: A setpoint value entered with the numeric keypad may be between valid setpoint values. The 469 detects this condition and stores a value that has been rounded to the near- HELP est valid setpoint value. To find the valid range and step for a given setpoint, simply press while the setpoint is being displayed.
  • Page 167 20 messages are already assigned, this message will appear. In order to add a message, one of the existing messages must be removed. PRESS [ENTER] TO REMOVE MESSAGE: If the decimal key is pressed in the S1 469 SETUP \ DEFAULT MESSAGES •...
  • Page 168 DEFAULT MESSAGE HAS BEEN REMOVED: Any time a default message is removed from the default message list, this message will appear as verification. DEFAULT MESSAGES 6 OF 20 ARE ASSIGNED: This message appears each time the S1 469 SETUP / DEFAULT •...
  • Page 169: Communications

    6.1.3 DATA FRAME FORMAT AND DATA RATE One data frame of an asynchronous transmission to or from an 469 is default to 1 start bit, 8 data bits, and 1 stop bit. This produces a 10 bit data frame. This is important for transmission through modems at high bit rates (11-bit data frames are not supported by Hayes modems at bit rates of greater than 300 bps).
  • Page 170: Data Packet Format

    If an 469 Modbus slave device receives a transmission in which an error is indicated by the CRC-16 calcu- lation, the slave device will not respond to the transmission. A CRC-16 error indicates than one or more bytes of the transmission were received incorrectly and thus the entire transmission should be ignored in order to avoid the 469 performing any incorrect operation.
  • Page 171: Algorithm

    (i.e. all slaves start listening for a new transmission from the master). Thus at 9600 baud a delay of greater than 3.5 × 1 / 9600 × 10 = 3.65 ms will cause the communication link to be reset. GE Power Management 469 Motor Management Relay...
  • Page 172: Supported Modbus Functions

    Read Coil and Input Status 469 Implementation: Read Relay Coil and Digital Input Status For the 469 implementation of Modbus, these commands can be used to read Relay Coil Status or Digital Input Status. a) FUNCTION 01 The standard implementation requires the following: slave address (one byte), function code (one byte), start- ing relay coil (two bytes), number of coils to read (two bytes), and CRC (two bytes).
  • Page 173 53 93 CRC calculated by the slave If STARTING RELAY COIL (STARTING DIGITAL INPUT) of Zero is entered, then 469 will default it to One. If the NUMBER OF RELAYS (NUMBER OF DIGITAL INPUTS) requested exceeds the number of relays available then user is prompted with a “ILLEGAL DATA” message.
  • Page 174 11 FUNCTION CODE read relay coil status BYTE COUNT 2 byte bit mask BIT MASK 71 01 bit mask of requested digital input C5 B9 CRC calculated by the slave 469 Motor Management Relay GE Power Management...
  • Page 175 SLAVE ADDRESS response message from slave 11 FUNCTION CODE read relay coil status BYTE COUNT 2 byte bit mask BIT MASK bit mask of requested digital input 63 90 CRC calculated by the slave GE Power Management 469 Motor Management Relay...
  • Page 176: Function Codes 03/04: Read Setpoints/Actual Values

    Actual Value ("input registers"). Holding and input registers are 16 bit (two byte) values transmitted high order byte first. Thus all 469 Setpoints and Actual Values are sent as two bytes. The maximum number of registers that can be read in one transmission is 125. Function codes 03 and 04 are configured to read set- points or actual values interchangeably because some PLCs do not support both function codes.
  • Page 177: Function Code 05: Execute Operation

    469 Implementation: Execute Operation This function code allows the master to request an 469 to perform specific command operations. The com- mand numbers listed in the Commands area of the memory map correspond to operation code for function code 05.
  • Page 178: Function Code 06: Store Single Setpoint

    Preset Single Register 469 Implementation: Store Single Setpoint This command allows the master to store a single setpoint into the memory of an 469. The slave response to this function code is to echo the entire master transmission. MESSAGE FORMAT AND EXAMPLE Request slave 11 to store the value 01F4 in Setpoint address 1180.
  • Page 179: Function Code 07: Read Device Status

    This is a function used to quickly read the status of a selected device. A short message length allows for rapid reading of status. The status byte returned will have individual bits set to 1 or 0 depending on the status of the slave device. 469 General Status Byte: Bit No. Description...
  • Page 180: Function Code 08: Loopback Test

    6.2.7 FUNCTION CODE 08: LOOPBACK TEST Modbus Implementation: Loopback Test 469 Implementation: Loopback Test This function is used to test the integrity of the communication link. The 469 will echo the request. MESSAGE FORMAT AND EXAMPLE Loopback test from slave 11. MASTER TRANSMISSION: BYTES...
  • Page 181: Function Code 16: Store Multiple Setpoints

    Modbus allows up to a maximum of 60 holding registers to be stored. The 469 response to this function code is to echo the slave address, function code, starting address, the number of Setpoints stored, and the CRC.
  • Page 182: Function Code 16: Performing Commands

    16. To perform this operation using function code 16 (10H), a certain sequence of commands must be written at the same time to the 469. The sequence consists of: command function register, command operation register and command data (if required). The command function register must be written with the value of 5 indicating an execute operation is requested.
  • Page 183: Error Responses

    6.3.1 DESCRIPTION When an 469 detects an error other than a CRC error, a response will be sent to the master. The MSbit of the FUNCTION CODE byte will be set to 1 (i.e. the function code sent from the slave will be equal to the function code sent from the master plus 128).
  • Page 184: Memory Map

    6.4.1 MEMORY MAP INFORMATION The data stored in the 469 is grouped as Setpoints and Actual Values. Setpoints can be read and written by a master computer. Actual Values are read only. All Setpoints and Actual Values are stored as two-byte values.
  • Page 185: Event Recorder

    6.4.4 WAVEFORM CAPTURE The 469 stores a number of cycles of A/D samples each time a trip occurs in a trace buffer, determined by the setpoint in S1 Preferences, Trace Memory Buffers. The Trace Memory Trigger is set up in S1 Preferences and this determines how many pre-trip and post-trip cycles are stored.
  • Page 186 6.4 MEMORY MAP 6 COMMUNICATIONS 6.4.5 469 MEMORY MAP Table 6–1: 469 MEMORY MAP (Sheet 1 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE Product ID (Addresses 0000 to 007F) PRODUCT ID 0000 Product Device Code...
  • Page 187 6 COMMUNICATIONS 6.4 MEMORY MAP Table 6–1: 469 MEMORY MAP (Sheet 2 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE Actual Values (Addresses 0200 -0FFF) MOTOR 0200 Motor Status FC133 STATUS 0201 Motor Thermal Capacity Used...
  • Page 188 6.4 MEMORY MAP 6 COMMUNICATIONS Table 6–1: 469 MEMORY MAP (Sheet 3 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE LAST TRIP 0243 Pre-Trip Real Power –50000 50000 DATA ALARM 0245 Pre-Trip Reactive Power –50000...
  • Page 189 6 COMMUNICATIONS 6.4 MEMORY MAP Table 6–1: 469 MEMORY MAP (Sheet 4 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE STATUS 027E RTD #12 Alarm Status FC123 continued 027F Open RTD Sensor Alarm Status...
  • Page 190 6.4 MEMORY MAP 6 COMMUNICATIONS Table 6–1: 469 MEMORY MAP (Sheet 5 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE START 02B3 Time Between Starts Lockout Time BLOCKS 02B4 Restart Block Lockout 50000 continued...
  • Page 191 6 COMMUNICATIONS 6.4 MEMORY MAP Table 6–1: 469 MEMORY MAP (Sheet 6 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE TEMPERA- 0329 RTD #9 Temperature –50 °C TURE 032A RTD #10 Temperature –50 °C...
  • Page 192 6.4 MEMORY MAP 6 COMMUNICATIONS Table 6–1: 469 MEMORY MAP (Sheet 7 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE POWER 0376 Apparent Power 65535 METERING 0377 MWh Consumption 999999999 continued 0379 Mvarh Consumption...
  • Page 193 6 COMMUNICATIONS 6.4 MEMORY MAP Table 6–1: 469 MEMORY MAP (Sheet 8 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE 03E0 RTD # 1 Max. Temperature –50 °C MAXIMUMS 03E1 RTD # 2 Max. Temperature –50...
  • Page 194 6.4 MEMORY MAP 6 COMMUNICATIONS Table 6–1: 469 MEMORY MAP (Sheet 9 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE 0424 Reserved 042F Reserved TRIP 0430 Total Number of Trips 50000 COUNTERS 0431 Incomplete Sequence Trips...
  • Page 195 6 COMMUNICATIONS 6.4 MEMORY MAP Table 6–1: 469 MEMORY MAP (Sheet 10 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE 049F Reserved TIMERS 04A0 Motor Running Hours 100000 04A2 Time Between Starts Timer 04A3...
  • Page 196 6.4 MEMORY MAP 6 COMMUNICATIONS Table 6–1: 469 MEMORY MAP (Sheet 11 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE 100F Reserved RS485 1010 Slave Address SERIAL 1011 Computer RS485 Baud Rate FC101 PORTS...
  • Page 197 6 COMMUNICATIONS 6.4 MEMORY MAP Table 6–1: 469 MEMORY MAP (Sheet 12 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE MESSAGE 10D4 Reserved SCRATCHPAD continued 10DF Reserved 10E0 1st & 2nd Char of 5th Scratchpad Message ‘Mu’...
  • Page 198 6.4 MEMORY MAP 6 COMMUNICATIONS Table 6–1: 469 MEMORY MAP (Sheet 13 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE 11BF Reserved POWER 11C0 Nominal System Frequency FC107 SYSTEM 11C1 System Phase Sequence FC124...
  • Page 199 6 COMMUNICATIONS 6.4 MEMORY MAP Table 6–1: 469 MEMORY MAP (Sheet 14 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE REMOTE TRIP 127A 1st and 2nd char. of Remote Trip Name 65535 ‘Re’ 127B 3rd and 4th char.
  • Page 200 6.4 MEMORY MAP 6 COMMUNICATIONS Table 6–1: 469 MEMORY MAP (Sheet 15 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE DIGITAL 12F3 1st and 2nd char. of Counter Units Name 65535 ‘Un’ COUNTERS 12F4 3rd and 4th char.
  • Page 201 6 COMMUNICATIONS 6.4 MEMORY MAP Table 6–1: 469 MEMORY MAP (Sheet 16 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE GENERAL 1366 1st and 2nd char. of General Switch B Name 65535 ‘Ge’ SWITCH B 1367 3rd and 4th char.
  • Page 202 6.4 MEMORY MAP 6 COMMUNICATIONS Table 6–1: 469 MEMORY MAP (Sheet 17 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE GENERAL 13D3 General Switch D Trip Relays FC111 SWITCH D 13D4 General Switch D Trip Delay...
  • Page 203 6 COMMUNICATIONS 6.4 MEMORY MAP Table 6–1: 469 MEMORY MAP (Sheet 18 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE O/L CURVE 15AF Standard Overload Curve Number SETUP 15B0 Time to Trip at 1.01 x FLA...
  • Page 204 6.4 MEMORY MAP 6 COMMUNICATIONS Table 6–1: 469 MEMORY MAP (Sheet 19 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE 163F Reserved SHORT 1640 Short Circuit Trip FC115 CIRCUIT TRIP 1641 Overreach Filter FC103...
  • Page 205 6 COMMUNICATIONS 6.4 MEMORY MAP Table 6–1: 469 MEMORY MAP (Sheet 20 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE CURRENT 1680 Current Unbalance Alarm FC115 UNBALANCE 1681 Current Unbalance Alarm Relays FC113 1682...
  • Page 206 6.4 MEMORY MAP 6 COMMUNICATIONS Table 6–1: 469 MEMORY MAP (Sheet 21 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE ACCELERA- 16D0 Acceleration Timer Trip FC115 TION TIMER 16D1 Acceleration Timer Trip Relays FC111...
  • Page 207 6 COMMUNICATIONS 6.4 MEMORY MAP Table 6–1: 469 MEMORY MAP (Sheet 22 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE RTD #1 1799 1st and 2nd char. of RTD #1 Name 65535 ‘ ‘...
  • Page 208 6.4 MEMORY MAP 6 COMMUNICATIONS Table 6–1: 469 MEMORY MAP (Sheet 23 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE RTD #4 17F0 RTD #4 Application FC121 17F1 RTD #4 Alarm FC115 17F2 RTD #4 Alarm Relays...
  • Page 209 6 COMMUNICATIONS 6.4 MEMORY MAP Table 6–1: 469 MEMORY MAP (Sheet 24 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE RTD #6 1839 1st and 2nd char. of RTD #6 Name 65535 ‘ ‘...
  • Page 210 6.4 MEMORY MAP 6 COMMUNICATIONS Table 6–1: 469 MEMORY MAP (Sheet 25 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE RTD #9 1890 RTD #9 Application FC121 1891 RTD #9 Alarm FC115 1892 RTD #9 Alarm Relays...
  • Page 211 6 COMMUNICATIONS 6.4 MEMORY MAP Table 6–1: 469 MEMORY MAP (Sheet 26 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE RTD #11 18D9 1st and 2nd char. of RTD #11 Name 65535 ‘ ‘...
  • Page 212 6.4 MEMORY MAP 6 COMMUNICATIONS Table 6–1: 469 MEMORY MAP (Sheet 27 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE RTD HIGH 1936 RTD #2 Hi Alarm Level °C ALARMS 1937 Reserved continued 1938...
  • Page 213 6 COMMUNICATIONS 6.4 MEMORY MAP Table 6–1: 469 MEMORY MAP (Sheet 28 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE UNDER 1960 Undervoltage Active Only If Bus Energized FC103 VOLTAGE 1961 Undervoltage Alarm FC115...
  • Page 214 6.4 MEMORY MAP 6 COMMUNICATIONS Table 6–1: 469 MEMORY MAP (Sheet 29 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE 19BB Reserved 19CF Reserved POWER 19D0 Block Power Factor Element from Start 5000 FACTOR...
  • Page 215 6 COMMUNICATIONS 6.4 MEMORY MAP Table 6–1: 469 MEMORY MAP (Sheet 30 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE 1A1A Reserved 1A1F Reserved REVERSE 1A20 Block Reverse Power From Start 5000 POWER 1A21...
  • Page 216 6.4 MEMORY MAP 6 COMMUNICATIONS Table 6–1: 469 MEMORY MAP (Sheet 31 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE STARTER 1A94 Supervision of Trip Coil FC142 FAILURE 1A95 Starter Failure Alarm Events FC103...
  • Page 217 6 COMMUNICATIONS 6.4 MEMORY MAP Table 6–1: 469 MEMORY MAP (Sheet 32 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE PULSE 1B16 Running Time Pulse Relay FC144 OUTPUT 1B17 Running Time Pulse Interval 50000...
  • Page 218 6.4 MEMORY MAP 6 COMMUNICATIONS Table 6–1: 469 MEMORY MAP (Sheet 33 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE ANALOG 1B6E RTD #3 Minimum –50 °C –50 OUTPUTS 1B6F RTD #3 Maximum –50 °C...
  • Page 219 6 COMMUNICATIONS 6.4 MEMORY MAP Table 6–1: 469 MEMORY MAP (Sheet 34 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE ANALOG 1BA0 Analog Input 1 Maximum –50000 50000 50000 OUTPUTS 1BA2 Analog Input 2 Minimum –50000...
  • Page 220 6.4 MEMORY MAP 6 COMMUNICATIONS Table 6–1: 469 MEMORY MAP (Sheet 35 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE ANALOG 1BEC RTD #10 Minimum (in Fahrenheit) –58 °F –57 OUTPUTS 1BED RTD #10 Maximum (in Fahrenheit) –58...
  • Page 221 6 COMMUNICATIONS 6.4 MEMORY MAP Table 6–1: 469 MEMORY MAP (Sheet 36 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE ANALOG 1C4B Analog Input 2 Setup FC129 INPUT 2 1C4C Reserved 1C4F Reserved 1C50 1st and 2nd char.
  • Page 222 6.4 MEMORY MAP 6 COMMUNICATIONS Table 6–1: 469 MEMORY MAP (Sheet 37 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE ANALOG 1C9F Analog Input 3 Trip FC115 INPUT 3 1CA0 Analog Input 3 Trip Relays...
  • Page 223 6 COMMUNICATIONS 6.4 MEMORY MAP Table 6–1: 469 MEMORY MAP (Sheet 38 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE × CT PRE-FAULT 1D10 Pre-Fault Current Phase A 2000 VALUES × CT 1D11 Pre-Fault Current Phase B 2000 ×...
  • Page 224 6.4 MEMORY MAP 6 COMMUNICATIONS Table 6–1: 469 MEMORY MAP (Sheet 39 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE FAULT 1D7D Fault Bearing RTD Temperature (in Fahrenheit) –58 °F VALUES 1D7E Fault Other RTD Temperature (in Fahrenheit) –58...
  • Page 225 6 COMMUNICATIONS 6.4 MEMORY MAP Table 6–1: 469 MEMORY MAP (Sheet 40 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE Speed2 Time to Trip at 10.0 × FLA SPEED2 1E36 999999 O/L SETUP Speed2 Time to Trip at 15.0 × FLA...
  • Page 226 6.4 MEMORY MAP 6 COMMUNICATIONS Table 6–1: 469 MEMORY MAP (Sheet 41 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE ANALOG 1F0A Analog In Differential 1-2 Block from Start 5000 INPUT 1-2 1F0B Analog In Differential 1-2 Alarm FC115 DIFF.
  • Page 227 6 COMMUNICATIONS 6.4 MEMORY MAP Table 6–1: 469 MEMORY MAP (Sheet 42 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE Event Recorder / Trace Memory (Addresses 3000 -3FFF) EVENT 3000 Event Recorder Last Reset (2 words)
  • Page 228 6.4 MEMORY MAP 6 COMMUNICATIONS Table 6–1: 469 MEMORY MAP (Sheet 43 of 43) GROUP ADDR DESCRIPTION MIN. MAX. STEP UNITS FORMAT DEFAULT (HEX) VALUE CODE EVENT … RECORDER 30DF Reserved continued 30E0 Event Temp. of Hottest Stator RTD (in Fahr.) –58...
  • Page 229: Memory Map Format Codes

    6 COMMUNICATIONS 6.4 MEMORY MAP 6.4.6 469 MEMORY MAP FORMAT CODES Table 6–2: MEMORY MAP DATA FORMATS (Sheet 1 of 14) Table 6–2: MEMORY MAP DATA FORMATS (Sheet 2 of 14) FORMAT TYPE DEFINITION FORMAT TYPE DEFINITION CODE CODE 16 bits...
  • Page 230 Unsigned OFF / ON or NO/YES SELECTION 10 Tachometer 16 bit integer 11 General Sw. A 0 Off / No 12 General Sw. B 1 On / Yes 13 General Sw. C 6-62 469 Motor Management Relay GE Power Management...
  • Page 231 8 RTD #8 FC117 Unsigned RESET MODE 9 RTD #9 16 bit integer 10 RTD #10 0 All Resets 11 RTD #11 1 Remote Reset Only 12 RTD #12 2 Keypad Reset Only GE Power Management 469 Motor Management Relay 6-63...
  • Page 232 19 RTD #4 1 Shorted 20 RTD #5 FC132 Unsigned TRIP COIL SUPERVISION STATUS 21 RTD #6 16 bit integer 22 RTD #7 0 No Coil 23 RTD #8 1 Coil 24 RTD #9 6-64 469 Motor Management Relay GE Power Management...
  • Page 233 76 RTD 12 Alarm 32 RTD 11 Trip 77 Open RTD Alarm 33 RTD 12 Trip 78 Short/Low RTD Alarm 34 Undervoltage Trip 79 Undervoltage Alarm 35 Overvoltage Trip 80 Overvoltage Alarm GE Power Management 469 Motor Management Relay 6-65...
  • Page 234 3 R3 Auxiliary 126 RTD 7 High Alarm 4 R4 Alarm 127 RTD 8 High Alarm 5 R5 Block Start 128 RTD 9 High Alarm 6 R6 Service 129 RTD 10 High Alarm 6-66 469 Motor Management Relay GE Power Management...
  • Page 235 0 Disabled 1 S2 Close 2 S2 Open/Close FC143 Unsigned SINGLE VT SELECTION 16 bit integer 0 Off 1 AN (Wye) AB (Delta) 2 BN (Wye) BC (Delta) 3 CN (Wye) N/A (Delta) GE Power Management 469 Motor Management Relay 6-67...
  • Page 237: Testing

    469 hardware while also testing firmware/hardware interaction in the process. Since the 469 is packaged in a drawout case, a demo case (metal carry case in which an 469 may be mounted) may be useful for creating a portable test set. Testing of the relay during commissioning using a primary injection test set will ensure that CTs and wiring are correct and complete.
  • Page 238: Hardware Functional Testing

    7.2 HARDWARE FUNCTIONAL TESTING 7.2.1 PHASE CURRENT ACCURACY TEST The 469 specification for phase current accuracy is ±0.5% of 2 × CT when the injected current is less than 2 × CT. Perform the steps below to verify accuracy. 1. Alter the following setpoint: S2 SYSTEM SETUP\CURRENT SENSING\PHASE CT PRIMARY: 1000A 2.
  • Page 239: Ground (1A/5A) And Differential Accuracy Test

    7.2.3 GROUND (1A/5A) AND DIFFERENTIAL ACCURACY TEST The 469 specification for differential current and 1 A/5 A ground current input accuracy is ±0.5% of 1 × CT for the 5 A input and 0.5% of 5 × CT for the 1 A input. Perform the steps below to verify accuracy.
  • Page 240: Ge Power Management 50:0.025 Ground Accuracy Test

    7 TESTING 7.2.4 GE POWER MANAGEMENT 50:0.025 GROUND ACCURACY TEST The 469 specification for GE Power Management 50:0.025 ground current input accuracy is ±0.5% of CT rated primary (25 A). Perform the steps below to verify accuracy. 1. Alter the following setpoint: S2 SYSTEM SETUP\CURRENT SENSING\GROUND CT: 50:0.025...
  • Page 241 10 Ω COPPER ° CELSIUS ° FAHRENHEIT 7.10 Ω –50°C –58°F 9.04 Ω 0°C 32°F 10.97 Ω 50°C 122°F 12.90 Ω 100°C 212°F 14.83 Ω 150°C 302°F 16.78 Ω 200°C 392°F 18.73 Ω 250°C 482°F GE Power Management 469 Motor Management Relay...
  • Page 242: Digital Inputs And Trip Coil Supervision

    Coil 7.2.7 ANALOG INPUTS AND OUTPUTS The 469 specification for analog input and analog output accuracy is ±1% of full scale. Perform the steps below to verify accuracy. Verify the Analog Input +24 V DC with a voltmeter. a) 4-20 mA 1.
  • Page 243 OUTPUT AMMETER READING (mA) ANALOG READING (units) FORCE READING INPUT VALUE READING 0 mA 0 mA 0.25 mA 250 mA 0.50 mA 500 mA 0.75 mA 750 mA 100% 1.00 mA 1000 mA GE Power Management 469 Motor Management Relay...
  • Page 244: Output Relays

    R1 Trip R2 Auxiliary R3 Auxiliary R4 Alarm R5 Block Start R6 Service All Relays No Relays R6 Service relay is failsafe or energized normally, operating R6 causes it to de-energize. NOTE 469 Motor Management Relay GE Power Management...
  • Page 245: Additional Functional Testing

    7.3.1 OVERLOAD CURVE TEST The 469 specification for overload curve timing accuracy is ±100 ms or ±2% of time to trip. Pickup accuracy is as per the current inputs (±0.5% of 2 × CT when the injected current is less than 2 × CT and ±1% of 20 × CT when the injected current is ≥...
  • Page 246: Power Measurement Test

    Va = 120 V ∠288° Va = 120 V ∠288° kvar 3519 Vb = 120 V ∠48° Vb = 120 V ∠48° kvar Vc = 120 V ∠168° Vc = 120 V ∠168° 7-10 469 Motor Management Relay GE Power Management...
  • Page 247: Unbalance Test

    7 TESTING 7.3 ADDITIONAL FUNCTIONAL TESTING 7.3.3 UNBALANCE TEST The 469 measures the ratio of negative sequence current ( I ) to positive sequence current ( I ). This value as a percent is used as the unbalance level when motor load exceeds FLA. When the average phase current is below FLA, the unbalance value is derated to prevent nuisance tripping as positive sequence current is much smaller and negative sequence current remains relatively constant.
  • Page 248: Voltage Phase Reversal Test

    Ic = 0.5 A ∠113° Ic = 2.5 A ∠113° 7.3.4 VOLTAGE PHASE REVERSAL TEST The 469 can detect voltage phase rotation and protect against phase reversal. To test the phase reversal ele- ment, perform the following steps: 1. Alter the following setpoints:...
  • Page 249: Short Circuit Test

    7.3 ADDITIONAL FUNCTIONAL TESTING 7.3.5 SHORT CIRCUIT TEST The 469 specification for short circuit timing is +50 ms. The pickup accuracy is as per the phase current inputs. Perform the steps below to verify the performance of the short circuit element.
  • Page 251: Installation/Upgrade

    Windows 3.1 Users must ensure that SHARE.EXE is installed. NOTE 469PC can be installed from either the GE Power Management Products CD or from the GE Power Manage- ment website at www.GEindustrial.com/pm. If you are using legacy equipment without web access or a CD, 3.5”...
  • Page 252: Checking If Installation/Upgrade Is Required

    If 469PC is already installed, run the program and check if it needs upgrading as follows: 1. While 469PC is running, insert the GE Power Management Products CD and allow it to autostart (alter- nately, load the D:\index.htm file into your default web browser, OR Go to the GE Power Management website at www.GEindustrial.com/pm (preferred method).
  • Page 253: Installing/Upgrading 469Pc

    469PC is installed, installation from the web is preferred. Figure 8–1: GE POWER MANAGEMENT WELCOME SCREEN 2. Click the Index by Product Name item from the main page and select 469 Motor Management Relay from the product list to open the 469 product page.
  • Page 254: Configuration

    6. To begin communications, click the ON button in the Communication section of the dialog box. The status section indicates the communications status. If communications are established, the message “469PC is now talking to a 469” is displayed. As well, the status at the bottom right hand corner of the screen indi- cates “Communicating”.
  • Page 255: Using 469Pc

    Enter the filename under which the setpoints are saved in the File Name box or select any displayed file names to update them. All 469 setpoint files should have the extension 469 (for exam- ple, motor1.469). Click OK to proceed.
  • Page 256: Firmware Upgrades

    8.3.2 469 FIRMWARE UPGRADES Prior to downloading new firmware to the 469, it is necessary to save the 469 setpoints to a file (see the previ- ous section). Loading new firmware into the 469 flash memory is accomplished as follows: 1.
  • Page 257: Loading Setpoints From A File

    1. Select the File > Open menu item. 2. 469PC will launch the Open dialog box listing all filenames in the 469 default directory with the 469 exten- sion. Select the setpoint file to download and click OK to continue.
  • Page 258: Entering Setpoints

    8.3 USING 469PC 8 469 PC SOFTWARE 8.3.4 ENTERING SETPOINTS The following example illustrates how setpoints are entered and edited from the 469PC software. 1. Select the Setpoint > Digital Inputs menu item. 2. Click the Input 1 tab to configure Digital Input 1 and select DIGITAL Counter from the Function menu.
  • Page 259: Upgrading Setpoint Files To New Revision

    8 469 PC SOFTWARE 8.3 USING 469PC 8.3.5 UPGRADING SETPOINT FILES TO NEW REVISION It may be necessary to upgrade the revision code for a previously saved setpoint file after the 469 firmware has been upgraded. 1. Establish communications with the relay.
  • Page 260 SETPOINTS 1. Select the File > Open menu item and open a previously saved setpoint file, OR establish communications with the 469. 2. Select the File > Print Setup menu item, select either Setpoints (All) or Setpoints (Enabled Features) and click OK.
  • Page 261 8.3 USING 469PC 8.3.7 TRENDING Trending from the 469 can be accomplished via the 469PC software. Many different parameters can be trended and graphed at sampling periods ranging from 1 second up to 1 hour. The parameters which can be Trended by the 469PC software are:...
  • Page 262 8.3 USING 469PC 8 469 PC SOFTWARE 5. Select the Sample Rate through the pull-down menu, click the checkboxes of the graphs to be displayed, and select RUN to begin the trending sampling. MODE SELECT LEVEL WAVEFORM Click on these buttons to view...
  • Page 263: Waveform Capture

    Waveform Capture window. 2. The waveform of Phase A current of the last 469 trip will appear. The date and time of this trip is displayed on the top of the window. The RED vertical line indicates the trigger point of the relay.
  • Page 264 8.3 USING 469PC 8 469 PC SOFTWARE MODE SELECT Click on these buttons to view Cursor 1, Cursor 2, or Delta (difference) WAVEFORM values for the graph The waveform data from the 469 relay TRIGGER DATE/TIME TRIGGER AGENT Click to manually trigger and...
  • Page 265: Phasors

    8 469 PC SOFTWARE 8.3 USING 469PC 8.3.9 PHASORS The 469PC software can be used to view the phasor diagram of three phase currents and voltages. The pha- sors are for: • Phase Voltages A, B, and C • Phase Currents A, B, and C 1.
  • Page 266: Event Recording

    8.3.10 EVENT RECORDING The 469 event recorder can be viewed with the 469PC software. The event recorder stores motor and system information each time an event occurs (e.g. motor trip). Up to 40 events can be stored, where EVENT01 is the most recent and EVENT40 is the oldest.
  • Page 267: Troubleshooting

    8 469 PC SOFTWARE 8.3 USING 469PC 8.3.11 TROUBLESHOOTING This section provides some procedures for troubleshooting the 469PC when troubles are encountered within the Windows environment (for example, General Protection Fault (GPF), Missing Window, Problems in Opening/Saving Files, and Application Error messages).
  • Page 269: Commissioning Summary

    APPENDIX A A.1 COMMISSIONING APPENDIX A APPENDIX AA.1 COMMISSIONING A.1.1 COMMISSIONING SUMMARY Table A–1: SETPOINTS PAGE 1 – 469 SETUP Table A–2: SETPOINTS PAGE 2 – SYSTEM SETUP DESCRIPTION DEFAULT USER VALUE DESCRIPTION DEFAULT USER VALUE PASSCODE CURRENT SENSING ----...
  • Page 270 General Switch Events Vibration Switch Alarm Unlatched General Switch Trip Assign Alarm Relays Alarm Assign Trip Relays Trip Vibration Switch Delay 5.0 s General Switch Trip Delay 5.0 s Vibration Switch Alarm Events 469 Motor Management Relay GE Power Management...
  • Page 271 Block Input From Start General Switch Alarm Assign Alarm Relays Alarm General Switch Alarm Delay 5.0 s General Switch Events General Switch Trip Assign Trip Relays Trip General Switch Trip Delay 5.0 s GE Power Management 469 Motor Management Relay...
  • Page 272 Force R2 Operation Time Static Force R3 Output Relay Disabled Force R3 Operation Time Static Force R4 Output Relay Disabled Force R4 Operation Time Static Force R5 Output Relay Disabled Force R5Operation Time Static 469 Motor Management Relay GE Power Management...
  • Page 273 1.00 Enable RTD Biasing? RTD Bias Minimum 40°C RTD Bias Center 130°C RTD Bias Maximum 155°C Thermal Capacity Alarm Assign Alarm Relays Alarm Thermal Cap. Alarm Level 75% Used Thermal Cap. Alarm Events GE Power Management 469 Motor Management Relay...
  • Page 274 Starting Differential Trip PU 0.10 x CT Undercurrent Trip Pickup 0.70 x FLA Starting Diff. Trip Delay 0 ms Undercurrent Trip Delay Running Diff. Trip Pickup 0.10 x CT Running Diff. Trip Delay 0 ms 469 Motor Management Relay GE Power Management...
  • Page 275 Accel. Timer From Start 10.0 s START INHIBIT Start Inhibit Block TC Used Margin JOGGING BLOCK Jogging Block Max. Starts/Hr. Permissible Time Between Starts Perm. 10 min. RESTART BLOCK Restart Block Restart Block Time GE Power Management 469 Motor Management Relay...
  • Page 276 RTD Short/Low Tmp. Alrm Events Platinum APPLICATION NAME ALARM ASSIGN ALARM ALARM TEMP . ALARM EVENTS RELAYS TRIP TRIP VOTING ASSIGN TRIP TRIP TEMP . HIGH ALARM HIGH ALARM HIGH ALARM RELAYS RELAYS TEMPERATURE 469 Motor Management Relay GE Power Management...
  • Page 277 Assign Alarm Relays Alarm Overvoltage Alarm Pickup 1.05 x Rated Overvoltage Alarm Delay 3.0 s Overvoltage Alarm Events Overvoltage Trip Assign Trip Relays Trip Overvoltage Trip Pickup 1.10 x Rated Overvoltage Trip Delay 3.0 s GE Power Management 469 Motor Management Relay...
  • Page 278 Stator Resistance Trip Delay 1.0 s Pole Pairs Torque Unit Newton-meter OVERTORQUE SETUP Overtorque Alarm Assign Alarm Relays Alarm Overtorque Alarm Level 4000.0 Nm Overtorque Alarm Delay 1.0 s Overtorque Alarm Events A-10 469 Motor Management Relay GE Power Management...
  • Page 279 Neg. kvarh Pulse Out. Interval 1 kvarh kW Demand Period 15 min. Running Time Pulse Relay kW Demand Alarm Running Time Pulse Interval Assign Alarm Relays Alarm kW Demand Limit 100 kW Alarm Events GE Power Management 469 Motor Management Relay A-11...
  • Page 280 ANALOG IN DIFF. Enabled? Name Units Minimum Maximum Block From Start Alarm Assign Alarm Relays Alarm Level Alarm Pickup Alarm Delay Alarm Events Trip Assign Trip Relays Trip Level Trip Pickup Trip Delay A-12 469 Motor Management Relay GE Power Management...
  • Page 281 Speed2 Acl. ISect @ Min. Vline 3.80 x FLA Speed2 Istall @ 100% Vline 6.00 x FLA Sp.2 Safe Stall @ 100% Vline 10.0 s Sp.2 Acl. ISect @ 100% Vline 5.00 x FLA GE Power Management 469 Motor Management Relay A-13...
  • Page 283: Appendix B B.1 Two-Phase Ct Configuration

    CTs (taking care that the CTs are still tied to ground at some point). Polarity is important. GE Power Management 469 Motor Management Relay...
  • Page 284 C. If on the other hand, phase B was lost, at the supply, phase A would be 180° out-of-phase with phase C and the vector addition would equal zero at phase B. 469 Motor Management Relay GE Power Management...
  • Page 285: Example

    The 469 thermal model provides integrated rotor and stator heating protection. If cooling time constants are supplied with the motor data they should be used. Since the rotor and stator heating and cooling is integrated into a single model, use the longer of the cooling time constants (rotor or stator).
  • Page 287: Current Transformers

    D.1.1 GROUND FAULT CTS FOR 50:0.025 A CTs that are specially designed to match the ground fault input of GE Power Management motor protection relays should be used to ensure correct performance. These CTs have a 50:0.025A (2000:1 ratio) and can sense low leakage currents over the relay setting range with minimum error.
  • Page 288: Ground Fault Cts For 5 A Secondary Ct

    For low resistance or solidly grounded systems, a 5 A secondary CT should be used. Two sizes are available with 5½” or 13” × 16” windows. Various Primary amp CTs can be chosen (50 to 250). GCT5 GCT16 DIMENSIONS DIMENSIONS 469 Motor Management Relay GE Power Management...
  • Page 289: Phase Cts

    Current transformers in most common ratios from 50:5 to 1000:5 are available for use as phase current inputs with motor protection relays. These come with mounting hardware and are also available with 1 A secondaries. Voltage class: 600 V BIL 10 kV. GE Power Management 469 Motor Management Relay...
  • Page 291 2–2: SEAL ON DRAWOUT UNIT........................2-1 IGURE 2–3: CASE AND UNIT IDENTIFICATION LABELS ..................2-2 IGURE 2–4: SINGLE AND DOUBLE 469 CUTOUT PANELS..................2-3 IGURE 2–5: BEND UP MOUNTING TABS ......................... 2-3 IGURE 2–6: PRESS LATCH TO DISENGAGE HANDLE ................... 2-4 IGURE 2–7: ROTATE HANDLE TO STOP POSITION ....................
  • Page 292: Figures And Tables

    E.1 FIGURES AND TABLES APPENDIX E 8–3: 469 FIRMWARE FILE FORMAT ......................8-6 IGURE 8–4: DIGITAL INPUT 1 – DIGITAL COUNTER SETPOINTS................8-8 IGURE 8–5: SETPOINT FILE VERSION........................8-9 IGURE 8–6: GRAPH ATTRIBUTE PAGE........................8-11 IGURE 8–7: TRENDING............................8-12 IGURE 8–8: TRENDING FILE SETUP ........................
  • Page 293: List Of Tables

    : 7–17 VOLTAGE PHASE REVERSAL TEST....................7-12 ABLE : 7–18 SHORT CIRCUIT TIMING ........................7-13 ABLE : A–1 SETPOINTS PAGE 1 – 469 SETUP ......................A-1 ABLE : A–2 SETPOINTS PAGE 2 – SYSTEM SETUP....................A-1 ABLE : A–3 SETPOINTS PAGE 3 – DIGITAL INPUTS ....................A-2 ABLE : A–4 SETPOINTS PAGE 4 –...
  • Page 295: Eu Declaration Of Conformity

    First Year of Manufacture: 1998 I the undersigned, hereby declare that the equipment specified above conforms to the above Directives and Standards Full Name: John Saunders Position: Manufacturing Manager Signature: Place: GE Power Management Date: 08/20/1998 GE Power Management 469 Motor Management Relay...
  • Page 297: Warranty Information

    Warranty shall not apply to any relay which has been subject to mis- use, negligence, accident, incorrect installation or use not in accor- dance with instructions nor any unit that has been altered outside a GE Power Management authorized factory outlet.
  • Page 299 ............1-5 clearing analog input data .......... 4-9 CONTACTOR, ALTERNATE WIRING ......2-19 description ............2-14, 4-80 CONTROL POWER difference setpoints ......... 4-81, 4-82 connection diagram ........... 2-9 maximums ............... 5-19 description ..............2-9 GE Power Management 469 Motor Management Relay...
  • Page 300 ..........6-17 DEMAND PERIOD ............4-75 motor speed ............. 5-23 DERATING FACTOR ..........4-42 software ..............8-16 DESCRIPTION ............1-1 tachometer ............... 5-23 DEVICE NUMBERS ............. 1-1 EVENT RECORDER DIAGNOSTIC MESSAGES ..........5-27 see EVENT RECORD above 469 Motor Management Relay GE Power Management...
  • Page 301 LED INDICATORS ............3-2 LINE VOLTAGE, MINIMUM .........4-30 LIST OF FIGURES ............E-1 HGF CTs ..............D-1 LIST OF TABLES ............E-3 HIGH INERTIAL LOAD ........4-26, 4-36 LOAD SHED HI-POT ..............2-22 frequency setpoints ..........4-65 GE Power Management 469 Motor Management Relay...
  • Page 302 MOTOR COOLING ............4-43 R5 START BLOCK ........... 2-18 MOTOR DERATING FACTOR ........4-42 R6 SERVICE ............2-18 MOTOR FLA ...............4-11 restart mode ............4-24 MOTOR INFORMATION, RESETTING ......4-10 setpoints ..............4-24 MOTOR LOAD specifications .............1-6 469 Motor Management Relay GE Power Management...
  • Page 303 ...............4-24 setpoints ..............4-64 R4 ALARM RELAY specifications ............1-7 description ...............2-18 tests ............... 7-12 operating ..............4-25 trip counter .............. 5-20 reset mode ...............4-24 PHASE ROTATION SETTINGS ........4-13 R5 START BLOCK RELAY GE Power Management 469 Motor Management Relay...
  • Page 304 RESET, REMOTE ............4-16 S11 MONITORING ............. 4-72 RESETTING THE 469 ..........4-24 S12 ANALOG I/O ............4-77 RESIDUAL ..............4-11 S13 469 TESTING ............4-83 RESIDUAL GROUND CONNECTION ......2-10 S14 TWO-SPEED MOTOR .......... 4-88 RESTART BLOCK S2 SYSTEM SETUP ........... 4-11 emergency restart ............4-16 S3 DIGITAL INPUTS ...........
  • Page 305 ............7-9 graph ..............4-32 phase current accuracy ..........7-2 multipliers ............... 4-33 phase reversal ............7-12 selection ..............4-29 power measurement ..........7-10 trip time ............4-29, 4-30 RTD accuracy ............7-4 START BLOCK RELAY GE Power Management 469 Motor Management Relay...
  • Page 306 ..............4-12 TYPICAL APPLICATIONS ..........1-1 VOLTAGE TRANSFORMER TYPICAL WIRING see VTs description ..............2-9 VOLTAGE TRANSFORMER RATIO ......4-12 wiring diagram ............2-8 VT CONNECTION TYPE ..........4-12 VT RATIO ..............4-12 469 Motor Management Relay GE Power Management viii...
  • Page 307 ..........4-5 phasors ..............5-15 trace memory trigger ..........4-5 single VT operation ..........4-12 WITHDRAWAL ............2-4 wye ................. 2-13 WYE VTs ..............2-13 WARRANTY ..............G-1 ZERO-SEQUENCE ..........2-11, 4-11 GE Power Management 469 Motor Management Relay...

Table of Contents