The 489 takes the information provided and create protection curves for any voltage
between the minimum and 100%. For values above the voltage in question, the 489
extrapolates the safe stall protection curve to 110% voltage. This current level is calculated
by taking the locked rotor current at 100% voltage and multiplying by 1.10. For trip times
above the 110% voltage level, the trip time of 110% will be used (see the figure below).
GE Multilin
1000
900
800
700
600
500
400
300
200
100
90
80
70
60
50
40
30
20
10
9
8
7
6
5
4
3
2
1
1
2
FIGURE 5–20: Voltage Dependent Overload Protection Curves
The safe stall curve is in reality a series of safe stall points for different voltages. For a given
voltage, there can be only one value of stall current, and therefore only one safe stall time.
489
VOLTAGE DEPENDENT
OVERLOAD PROTECTION CURVES
Custom Curve
Acceleration Intersect at 80%V
Acceleration Intersect at 100%V
Safe Stall Time at 80%V,
80%V Stall Current
Safe Stall Time at 100%V,
100%V Stall Current
Safe Stall Points
Extrapolated to 110%V
3
4
5
6
MULTIPLES OF FULL LOAD AMPS
489 GENERATOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETPOINTS
7
8
808831A3.CDR