CHAPTER 6: ACTUAL VALUES
Note
Ambient RTD12 Trip *
Bearing RTD 9 Trip *
Distance Zone 2 Trip
Hiset Phase O/C Trip
Loss of Excitation 2
Neut. U/V (3rd) Trip
* reflects the name as programmed
489 GENERATOR MANAGEMENT RELAY – INSTRUCTION MANUAL
Courtesy of NationalSwitchgear.com
HOTTEST OTHER
MESSAGE
RTD#11: 0°C
AMBIENT
MESSAGE
RTD#12 0°C
ANALOG INPUT 1
MESSAGE
E001: 0.0 Units
ANALOG INPUT 2
MESSAGE
E001: 0.0 Units
ANALOG INPUT 3
MESSAGE
E001: 0.0 Units
ANALOG INPUT 4
MESSAGE
E001: 0.0 Units
The 489 Event Recorder stores generator and system information each time an event
occurs. The description of the event is stored and a time and date stamp is also added to
the record.
The event recorder data may be inaccurate if 489 relay power-on time is less than
2 seconds.
The date and time stamping feature allows reconstruction of the sequence of events for
troubleshooting. Events include all trips, any alarm optionally (except Service Alarm, and
489 Not Inserted Alarm, which always records as events), loss of control power, application
of control power, thermal resets, simulation, serial communication starts/stops, and
general input control functions optionally.
is the most recent event and
E001
event records down until the 256th event is reached. The 256th event record is lost when
the next event occurs. This information can be cleared using
setpoint. The event record will not update if a digital input
CLEAR EVENT RECORD
programmed as Test Input is shorted.
Table 6–1: Cause of Events (Sheet 1 of 2)
Analog I/P 1 to 4 Trip *
Bearing RTD 10 Trip *
Field-Bkr Discr. Trip
Inadvertent Energization
Trip
Low Fwd Power Trip
Offline O/C Trip
Range: –50 to +250°C. Seen only if 1 or
E001
Range: –50 to +250°C. Seen only if 1 or
E001
Range: –50000 to 50000. Reflects the
Range: –50000 to 50000. Reflects the
Range: –50000 to 50000. Reflects the
Range: –50000 to 50000. Reflects the
is the oldest event. Each new event bumps the other
E256
S1 489 SETUP
TRIPS
Bearing RTD 7 Trip *
Differential Trip
Gnd Directional Trip
Input A to G Trip *
Neg Seq O/C Trip
Overfrequency Trip
more RTDs are set as Other.
more RTDs are set as Ambient.
Analog Input name. Not seen if
Analog Input 1 is disabled.
Analog Input name. Not seen if
Analog Input 2 is disabled.
Analog Input name. Not seen if
Analog Input 3 is disabled.
Analog Input name. Not seen if
Analog Input 4 is disabled.
CLEAR DATA
Bearing RTD 8 Trip *
Distance Zone 1 Trip
Ground O/C Trip
Loss of Excitation 1
Neutral O/V Trip
Overvoltage Trip