Installing a ground cable
4
Connecting Water Pipes
1. Connect the water pipes using thread connectors. The thread joints need to be sealed with raw
materials or thread adhesive.
2. Clean the external water pipes before connecting them to the water inlet and outlet pipes of the
coil pipes of the FusionCol8000.
3. Connect the water inlet and outlet pipes of the FusionCol8000 using thread connectors. When
connecting the water pipe, do not exert excessive force to prevent damage to the coil pipe.
(When connecting the pipes provided with the FusionCol8000, use two pipe wrenches or chain
pliers.)
4. Heat preservation measures must be taken at low temperatures to prevent water from freezing in
the water pipe.
5. The drainpipe must be wrapped with thermal insulation foam (including the buried parts).
1. Installing Water Pipes
The maximum
allowable installation
inclination of the
water seal is 15
degrees.
Install the water seal
in strict accordance
with the preceding
figure to avoid
reverse connection.
(1) Condensate drainpipe (DN25)
(2) Spray drainpipe (DN40)
(3) Spray water refill pipe (DN20)
5