4.7.2

Output data (master to inverter)

[Master output area (master → inverter)]
Address
(word boundary)
Word
(n: node address)
Bit
0
4(n-1)+256
1
4(n-1)+257
2
4(n-1)+258
3
4(n-1)+259
(1)
Control input command
Set control input command such as forward and reverse rotation commands.
Bit
Signal
Forward rotation
0
STF signal
command
Reverse rotation
1
STR signal
command
Pr. 59 = 0 (initial value) Low-speed operation command
Pr. 59 = 1, 2 ∗1
2
RL signal
Pr. 270 = 1 ∗2
Pr. 59 = 0 (initial value) Middle-speed operation command
3
RM signal
Pr. 59 = 1, 2 ∗1
Pr. 59 = 0 (initial value) High-speed operation command
4
RH signal
Pr. 59 = 1, 2 ∗1
Second function
5
RT signal
selection
Pr. 270 = 1 ∗2
6 to 8 — (not used) Always 0
9
MRS signal Output stop
10
— (not used) Always 0
PU operation interlock
Bit11
0
11
X12 signal
1
12 to 14 — (not used) Always 0
Resets the inverter when the setting of Bit15 is changed from 0 to 1 at
15
Error reset
occurrence of inverter error. Resetting the inverter resets the fault and initializes
the inverter status. (FL remote communication remains online.)
∗1
When Pr. 59 Remote function selection = "1" or "2", the functions of the RL, RM and RH signals are changed as given in the table.
∗2
When Pr. 270 Stop-on contact control selection = "1", functions of RL and RT signals are changed as in the table.
REMARKS
The values of each bit, "0" and "1," indicate "OFF" and "ON."
15
14
13
12
11
10
(2) Set frequency (0.01 Hz increments)
Description
Bit0
Forward rotation: 0 Reverse rotation: 0 Stop command
Forward rotation: 1 Reverse rotation: 0
Forward rotation: 0 Reverse rotation: 1
Forward rotation: 1 Reverse rotation: 1 Stop command
Remote setting (setting clear)
Stop-on contact selection 0
Remote setting (deceleration)
Remote setting (acceleration)
0: second function selection invalid,
1: second function selection valid
Stop-on contact selection 1
0: output shut off cancel, 1: output shut off
Signal Function/Operation
Operation mode
Forcibly switched to Network
operation mode
Network operation is allowed
Switching to the PU operation
mode is disabled
Operation mode (PU, NET)
switching is enabled
Output stop during Network
operation
Applications
9
8
7
6
5
(1) Control input command
— (not used)
— (not used)
Bit1
Command
Forward rotation
command
Reverse rotation
command
Parameter write
Parameter write is disabled
(Note that the Pr.297 setting is
available when Pr.296 ≠ "9999.")
Parameter write is enabled
(depending on Pr. 77 Parameter
write selection and each parameter
write conditions)
Cyclic transmission
4
3
2
1
0
Related Parameters
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27
Pr. 59
Pr. 270, Pr. 275, Pr. 276
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27
Pr. 59
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27
Pr. 59
Pr. 44 to Pr. 51
Pr. 270, Pr. 275, Pr. 276
Pr. 17
Refer
to
Page
141
111
113
139
111
113
111
113
143
139
143
4
51
57