I/O signal control

5.11.5 Detection of output frequency (SU, FU signal, Pr. 41 to Pr. 43)

The inverter's output frequency is detected, and the signals are output through FL remote communication.
Parameter
Name
Number
Up-to-frequency
41
sensitivity
Output frequency
42
detection
Output frequency
43
detection for reverse
rotation
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)
Set frequency
OFF
SU
Forward
rotation
Output signal
OFF
ON
FU
REMARKS
All signals are OFF during DC injection brake.
The output frequency to be compared with the set frequency is the output frequency before slip compensation is performed.
144
Initial Value
10%
6Hz
9999
Adjustment
range Pr.41
Time
ON
OFF
Pr.42
Reverse
rotation
OFF
OFF
ON
Setting Range
0 to 100%
Level where the SU signal turns ON.
0 to 400Hz
Frequency where the FU signal turns ON.
Frequency where the FU signal turns ON in reverse
0 to 400Hz
rotation.
9999
Same as Pr. 42 setting
(1)
Up-to-frequency sensitivity (SU signal, Pr. 41)
When the output frequency reaches the set frequency, the
up-to-frequency signal (SU) is output.
The Pr. 41 value can be adjusted within the range 0% to
±100% on the assumption that the set frequency is 100%.
This parameter can be used to ensure that the running
frequency has been reached to provide the operation start
signal etc. for related equipment.
(2)
Output frequency detection
(FU signal, Pr. 42, Pr. 43)
The output frequency detection signal (FU) is output when
the output frequency reaches or exceeds the Pr. 42 setting.
Time
This function can be used for electromagnetic brake
Pr.43
operation, open signal, etc.
Frequency detection that is dedicated to reverse operation
use can be set by setting detection frequency to Pr. 43. This
function
is
effective
electromagnetic brake operation between forward rotation
(rise) and reverse rotation (fall) during vertical lift operation,
etc.
When Pr. 43 ≠ "9999", the Pr. 42 setting is used for forward
rotation and the Pr. 43 setting is used for reverse rotation.
Description
for
switching
the
timing
of