z Apply voltage terminal ([CNA02])
When a power supply must be provided at the input device you want to connect, use the Apply
voltage terminal ([CNA02])
Load
resistance
*c
connected unit
*1: Make the power supply DC 12 to 24 V. Select a power supply capacity with an ample surplus for the
connected load.
Do not impress a voltage exceeding 24 V across pins 1-3.
*c: The allowable current is DC 5mA to 10mA. (Recommended: DC 5 mA)
Provide a load resistance such that the current becomes DC 10 mA or less.
Select very low current use contacts (usable at DC 12 V, DC 1 mA or less).
*d: The polarity is [+] for pin 1 and [-] for pin 3. Connect correctly.
When connected to Apply voltage terminals of multiple RB units with a connected unit, be sure
to make a branch outside the RB unit using a pull box, etc. as shown on below example.
Load
resistance
connected unit
DC power
*1
supply 12 - 24 V
-
+
DC power
supply 12 - 24 V
- (08 - 46) -
P.C.B
+
1
2
CNA02
-
3
*d
P.C.B
CNA
02
P.C.B
CNA
02
P.C.B
CNA
02