Fujitsu Airstage J-II Series Design & Technical Manual page 518

Small vrf system
Table of Contents

Advertisement

 To protect the compressor of the outdoor unit, carefully read and understand the following cautions that may affect
the operation of the compressor before executing the setting.
 When performing periodical settings like schedule settings for the following functions, perform the setting to all the
indoor units in the same refrigerant system simultaneously, conforming to the timing restriction described below.
<Corresponding function>
· Start operation
· Release indoor unit forced
thermostat off mode
 Forced thermostat OFF instruction
 Only one equipment can send these instructions for each refrigerant system.
 When these instructions are sent by multiple equipment, the system may not respond as instructed or may
malfunction.
„ SPECIFICATIONS
Power supply
Input Power (W)
Dimensions [H × W × D]: in. (mm)
Weight: lb. (g)
z Recommended operating environment
Temperature: °F (°C)
Humidity (%)
z Transmission specifications
Transmission speed
Cable
Network connector
More than 10 minutes must elapse
More than 10 minutes must elapse
2-3/8 × 10-5/8 × 6-15/16 (60 × 270 × 176)
Operating
Packaged
Packaged
®
BACnet
/ IP (ASHRAE 135 Annex J)
10 / 100 Mbps
Ethernet category 5 or higher STP
22AWG equivalent
RJ45
- (05 - 155) -
· Stop operation
· Set indoor unit forced thermostat
off mode
1ø AC 208-240 V 50/60 Hz
4.6
3 (1,200)
32 to 114.8 (0 to 46)
14 to 140 (-10 to 60)
0 to 95 (RH) ;
No condensation