Samsung AE RXYDEG Series Installation Manual page 33

Air to water heat pump mono outdoor unit
Table of Contents

Advertisement

Power Cable Specifications
1 phase
Outdoor unit
AE080RXYDEG
AE120RXYDEG
AE160RXYDEG
The power cable is not supplied with Air to water heat pump.
Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (Code
designation IEC:60245 IEC 57 / CENELEC:H05RN-F)
This Equipment complies with IEC 61000-3-12.
Indoor Unit
(Water Pump, Valve, Wired RMC)
MIM-E03CN
Booster Heater (3kw)
Booster Heater (~3kw)
 + Backup Heater (~3kw)
The Power cable is not supplied with the heat pump.
For power cable, use the grade H05RN-F materials in 1Ø system.
If you connect Backup Heater at separated power cable, you can reduce wire size. (Please refer to control kit installation
manual)
3 Phase
Outdoor unit
AE080RXYDGG
AE120RXYDGG
AE160RXYDGG
The power cable is not supplied with air to water heat pump.
Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (Code
designation IEC:60245 IEC 66 / CENELEC:H07RN-F)
This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to
3.3[MVA] at the interface point between the user's supply and the public system. It is the responsibility of the installer or
user of the equipment to ensure, by consultation with distribution network operator if necessary, that the equipment is
connected only to a supply with a short-circuit power Ssc greater than or equal to 3.3[MVA].
Rated
Voltage Range
Hz
Volts
Min
50
220-240
198
50
220-240
198
50
220-240
198
Load
Power supply
No Heater
1Ø, 220-240V,
Rated
Voltage Range
Hz
Volts
Min
50
380-415
342
50
380-415
342
50
380-415
342
MCA
Max
Min. Circuit Amps.
264
22 A
264
28 A
264
32 A
Power cable
2
mm
,wires
1.5 / 3
2.5 / 3
4.0 / 3
50Hz
6.0 / 3
6.0 / 3
8.0 / 3
MCA
Max
Min. Circuit Amps.
457
10 A
457
10 A
457
12 A
MFA
Max. Fuse Amps.
27.5 A
35 A
40 A
MAX. length
Type GL
m
A
<10m
10
10m<L<20m
10
<10m
20
10m<L<20m
20
<10m
40
10m<L<20m
40
MFA
Max. Fuse Amps.
16.1 A
16.1 A
16.1 A
33

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents