Samsung AE RXYDEG Series Installation Manual page 29

Air to water heat pump mono outdoor unit
Table of Contents

Advertisement

Calculating the pre-pressure of the expansion vessel
The pre-pressure(Pg) to be set depends on the maximum installation height difference(H) and is calculated as below :
Pg=(H/10+0.3) bar
Unit resistance and PHE resistance by glycol concentrate
The unit is composed of water pipes and PHE basically.
To ensure correct operation and predict the expected performance, Flow and Resistance table can be used and Flow and
Resistance characteristic is dependent on Glycol concentration.
70
60
50
40
30
20
10
0
5
10
15
AE120RXYD**/AE160RXYD**
70
60
50
40
30
20
10
0
5
10
15
20
Changing Glycol concentration can cause the pressure drop of the system and it can leads to make flow rate rather slow. Just
in case performance degration, installer shall be careful of flow rate changes.
AE080RXYD**
20
25
30
35
40
LPM
25
30
35
40
45
50
55
LPM
WATER
PG 10%
PG 20%
PG 30%
PG 40%
PG 45%
45
50
WATER
PG 10%
PG 20%
PG 30%
PG 40%
PG 45%
60
65
70
29