Piping work
Freeze protection
Freeze protection solutions must use propylene glycol with a toxicity rating of Class 1 as listed in Clinical Toxicology of
Commercial Products, 5th Edition.
Ethylene glycol is toxic and must not be used in the primary water circuit in case of any cross-contamination of
the potable circuit.
WARNING
Percent Propylene Glycol [wt. %]
0
10
20
30
36
40
43
48
Setting capacity and pre-pressure of the expansion vessel
When it is required to change the default pre-pressure of
the expansion vessel(1 bar), keep in mind the following
guidelines:
Use only dry nitrogen to set the expansion vessel pre-
pressure.
Inappropriate setting of the expansion vessel
pre-pressure will lead to malfunction of the system.
Therefore, the pre-pressure should only be adjusted by a
licensed installer.
Installation height
difference(a)
<7m
No pre-pressure adjustment required.
Actions required:
Pre-pressure must be increased, calculate the
appropriate value following by "Calculating
>7m
the pre-pressure of the expansion vessel".
Check if the water volume is lower than
maximum allowed water volume.
(a) Installation height difference: height difference(m) between the highest point of the water circuit and the indoor unit. If
the unit is located at the highest point of the installation, the installation height is considered 0m.
When Expansion vessel has a capacity 8 liters and 1bar pre-charged.
Water volume of total system for reliable performance is minimum 30 Liter(AE050RX****), 50 Liter(AE120/160RX****).
28
Freezing Points of Propylene Glycol - Water Mixtures
Freezing Point [ °F ]
32
26
20
10
0
-5
-10
-20
< 220 Litres
2.5
2.0
1.5
Operation range
1.0
0.5
0.0
150
200
Total water volume(ℓ)
Water volume
Actions required:
Pre-pressure must be decreased, calculate
according to "Calculating the pre-pressure of
the expansion vessel".
Check if the water volume is lower than
maximum allowed water volume.
Expansion vessel of the unit too small for the
installation.
Freezing Point [ °C ]
0
-3
-7
-12
-18
-20
-23
-29
250
300
> 220 Litres
350