1MRS750527-MUM
5.1.2.3.
5.1.2.4.
5.1.2.5.
Feeder Terminal
Technical Reference Manual, General
Interlocking LED texts can also be defined in the view illustrated above, but the
interlocking LED colors cannot be changed. For the operation of the interlocking
LED, refer to Section "Interlocking" on page 87.
For more information about the use of the editor, refer to the Relay
Mimic Editor manual (refer to Section "Related documents" on
page 10).

LON network configuration

The LON Network Tool is used for binding network variables between RED 500
terminals. Typically, LON is used for transferring status data between the terminals
for interlocking sequences running in the units, see Fig. 5.1.2.3.-1 below and Fig.
5.1.13.10.-1 on page 80.
Comm_Out
Comm_In
nv_state
nv_state
nv_state
>1
Blocking
Open
enable
Inter-
locking
Close
enable
Open
Reserve
I/O
Close
RE_ 54_
Fig. 5.1.2.3.-1 Communication between RED 500 terminals in station interlocking
For more information about the use of the tool, refer to the LNT 505
Operator's Manual (refer to Section "Related documents" on
page 10).

DNP 3.0 and Modbus configuration

Protocol Mapping Tool (PMT) is used for DNP 3.0 and Modbus configuration. PMT
is integrated in CAP 505. For more information about PMT, refer to CAP 505
Protocol Mapping Tool, Operation Manual (refer to Section "Related documents"
on page 10).

Rated frequency

The rated frequency of the feeder terminal is set in association with configuration
via a dialog box in the Relay Configuration Tool. The set rated frequency cannot be
changed afterwards via the HMI or serial communication, but it can be read via the
global control parameter "Rated frequency" of the feeder terminal.
LON
Comm_Out
Comm_In
nv_state
nv_state
nv_state
>1
Blocking
Open
enable
Inter-
locking
Close
enable
Open
Reserve
I/O
Close
RE_ 54_
REF 54_
Comm_In
Comm_Out
nv_state
nv_state
nv_state
>1
Blocking
Open
enable
Inter-
locking
Close
enable
Open
Reserve
I/O
Close
RE_ 54_
A050183