3.Latched Alarm, Blinking Leds; 4.Interlocking - ABB REF 54 Series Technical Reference Manual, General

Feeder terminal
Hide thumbs Also See for REF 54 Series:
Table of Contents

Advertisement

1MRS750527-MUM
5.1.16.3.
5.1.16.4.
Feeder Terminal
Technical Reference Manual, General
Fig. 5.1.16.2.-1 Example of a latched alarm with steady LED
Latched alarm, blinking LEDs
Latched, blinking alarms can be acknowledged after the rising edge of the ON
signal. The time stamp of the first alarm is recorded. If the ON signal is inactive,
acknowledgement clears the time stamp line of the alarm view and the
corresponding alarm LED. However, if the ON signal is active during
acknowledgement, the alarm LED mode turns stable and the time stamp is cleared.
Later, when the ON signal is deactivated, the alarm LED color will automatically
change to OFF color. An event is generated on the rising and falling edge of the ON
signal and by acknowledgement. The visual indication, including resetting, of this
alarm mode complies with the ISA-A standard.
Fig. 5.1.16.3.-1 Example 1 of a latched alarm with blinking LEDs
Fig. 5.1.16.3.-2 Example 2 of a latched alarm with blinking LEDs
Interlocking
The interlocking LED text can be defined in the same manner as for the other alarm
channels. The color of the interlocking LED is yellow and cannot be changed. The
normal LED state is inactive (no light). Furthermore, the interlocking LED has two
REF 54_
Alarind3_b
Alarind2_b
Alarind2_b
87