Specifications - NI FieldPoint FP-DO-400 Operating Instructions Manual

8-channel, 5 to 30 v discrete output module
Table of Contents

Advertisement

Specifications

These specifications are typical for the range –40 to +70 °C unless
otherwise noted.
Input Characteristics
Number of channels.......................... 8
Voltage range .................................... 5 to 30 VDC
10 to 30 V Voltage Range
Output impedance ...................... 0.3 Ohm
Maximum output current............ 2 A per channel,
Note
2
9 A
. For example, 1 A on all eight channels or 2 A on
two channels.
5 V Voltage Range
Output impedance ...................... 2 Ohms
Maximum output current............ 0.67 A per channel,
Note
1.35 A
0.67 A on three channels.
Output delay times ..................... 50
Isolation...................................... 3,000 Vrms
Safety isolation,
working voltage .......................... 250 Vrms, designed per IEC
Physical
Indicators .......................................... Green POWER and
Weight............................................... 140 g (4.8 oz.)
Power Requirements
Power from network module ............ 300 mW
© National Instruments Corp.
Sum of output currents squared must be less than
Sum of output currents squared must be less than
2
. For example, 0.4 A on all eight channels or
(0.3 volts drop at 1 A)
2
9 A
per module
2
1.35 A
per module
µ
s
1010 as double insulated
READY indicators, 8 green
output state indicators
7
FP-DO-400