Inspection of electrical and
mechanical accessories
69 | © 2019 ABB | 1SDH001000R0002 - ECN000109166 - Rev. D
Continued from the previous page
Figure 92 - Lubricating the opening hook
• In the case of deformed or rusty springs, rings missing or severe wear of the operating device, contact
ABB Sace.
Check the accessories:
1.
Check that the accessories are securely fixed to the circuit-breaker.
2.
Check that the accessories are connected correctly to the circuit-breaker.
3.
Make sure that the coils (YU-YO-YC) are in good condition (no excessive wear and tear, overheating,
rupture).
4.
Make sure that the mechanical operation counter functions correctly (if present) by operating the
circuit-breaker.
5.
Check the wear on the brushes of the gearmotor and if necessary replace them.
NOTE: it is advisable to replace the gear motor if it has performed more than 10000 spring
charging operations or reached 50% of the declared mechanical life of the circuit-breaker.