Event codes and recommendations

Below is a list of the event codes that your LWT instrument might display should a problem arise, and
recommended action for each event. The first letter of the code refers to NAMUR codes:
• F: Failures
• S: Function check
• C: Out of specifications
• M: Maintenance request
Table 4
Event codes and recommended action
No.
Event message
S080.000
Maximum level rate exceeded
S081.001
GpC alarm, last valid gpc used
F203.002
Sensor has lost surface echo
S088.003
No interface detected
S085.004
Emulsion has been detected
F234.005
Electronic failure or harsh env
S060.010
pV value out of range
C153.011
GpC currently in calibration
S083.012
too many echos detected
F233.013
Reference echo not detected
F210.016
Invalid device parameters
F236.017
Sensor NV Failure
S110.018
Successful sensor reboot
S062.019
Surface inside blocking distance
F237.020
Sensor Board communication error.
F233.023
Electronics NV Failure
S082.024
Weak echo amplitude
F232.025
Unconnected coupler or probe
S061.026
Surface inside safety distance
M30.031
Maintenance required
M011.033
temperature out of range
F230.034
First coupler seal leak
F235.035
Load sensor configuration failure
C151.036
Data Simulation warning
C150.037
alarm Simulation warning
M012.042
NV replace error.
M035.045
hMI validation test failure
F231.046
Broken probe or wrong length
M026.047
Build-up on probe
76
User Guide
Recommended action
Make sure max level rate matches the process
Check installation, GpC marker, process cond.
Check installation and parameter adjustments.
For information purposes only
For information purposes only
Check installation for vibrations or EMC interference
Check process conditions and device config.
Wait for calibration to finish.
Check installation or device parameters.
Check installation and coupler connection.
Enter valid parameters
the sensor should be replaced aSap
Successful sensor reboot
Check process conditions and device config.
Restart sensor. If condition persists, call aBB
the electronics must be replaced; call aBB.
Check installation and process conditions.
Check connection of head, coupler and probe
Check process conditions and/or device config.
Verify sensor functionality, clear diagn. Mess.
Check ambient temperature. Use remote option
Check coupler.
Restart sensor. If condition persists, call aBB
the Output value is derived from simulated value
alarm condition is being simulated by the device
Restart sensor. If condition persists, call aBB
Replace the hMI; call aBB.
Replace probe or adjust probe length.
Clean probe.