password' and for remote connection 'WHMI remote password'. Local connection is
allowed only from the Ethernet port called 'Local port'. Via the local connection user is
allowed to perform local control operations such as opening or closing circuit breaker.
From all other Ethernet ports only remote connections are allowed.
Passwords are settable for all predefined user categories. The password must contain at
least nine characters. The maximum number of characters is 20. Only the following
characters are accepted.
Numbers 0-9
Letters a-z, A-Z
Space
Special characters !"#%&'()*+´-./:;<=>?@[\]^_`{|}~
Table 8: Predefined user categories and default passwords
Username
VIEWER
OPERATOR
ENGINEER
ADMINISTRATOR
3.4

Setting IED and communication

3.4.1

Setting the communication between IEDs and PCM600

The communication between the IED and PCM600 is independent of the used
communication protocol within the substation or to the NCC. It can be seen as a second
channel for communication.
The media is always ETHERNET and communication is based on TCP/IP.
Each IED has multiple Ethernet connectors, and all Ethernet interfaces can be used to
connect PCM600.
When an Ethernet based station protocol is used, the PCM600 communication can use
the same Ethernet port and IP ADDRESS. The IED is able to separate the information
belonging to the PCM600 dialog.
To configure the physical connection and the IP addresses:
SSC600
Operation Manual
Note: User authorization is disabled by default and can be enabled via the
WHMI Main Menu > Configuration > Authorization > Passwords.
WHMI remote pass-
word
remote0001
remote0002
remote0003
remote0004
Note: For user authorization for PCM600, see PCM600 documentation.
WHMI local password
User rights
0001
Only view access
0002
Authorized to make op-
erations
0003
Allowed to change IED
parameters, but no op-
eration rights
0004
Full access
Commissioning