PDU8000 UPS Power Distribution Cabinet
User Manual
No.
4
5
6
7
8
9
10
Figure 5-8 Cable ties without sharp burs
Figure 5-9 Cable ties in the same direction
Issue 01 (2016-03-04)
Cable Binding Rule
shown in
Figure 5-8
and
Each output power cable bundle can contain 5–10 cables. If too many
cables are bound together, the cables may overheat due to poor heat
dissipation.
Extra cables are coiled neatly and easy to find.
Cables on the surface of a large cable bundle are neatly organized without
unnecessary crossover.
Cables are arranged in distinct layers and crossovers are avoided if
possible when cables in different colors are bound together, as shown in
Figure
5-10. Cables are arranged by thickness when arrangement by
thickness conflicts with arrangement by color.
Cables are reliably bound along the route, and the binding interval meets
the requirements in
Table
Power cables must be away from sharp components such as copper bars
and terminals to avoid scratching.
Cables must be bound at an interval of 300–500 mm using nylon cable ties
to avoid dangling.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Figure
5-9.
5-4.
5 Installation Guide
44