PDU8000 UPS Power Distribution Cabinet
User Manual
Figure 5-6 Leveling and tightening bolts
(1) Anchor bolt
Step 4 Secure the bolts used for securing the PDC and support using a socket wrench.
----End

5.4.5 (Optional) Combining Cabinets

Procedure
Step 1 Remove the front and rear doors of the PDC and level the PDC, as shown by (1) in
5-7.
Step 2 Install the four cabinet connecting plates at the front and rear of the PDC, as shown by (2) and
(3) in
Step 3 Reinstall the front and rear doors of the PDC.
Step 4 Use a torque wrench to tighten the bolts to a torque of 45 N· m in diagonal order.
Issue 01 (2016-03-04)
When cabinets need to be combined, just partially tighten the bolts.
Figure
5-7.
A connecting plate is initially secured by one screw. Remove the screw from the column in the
adjacent cabinet to secure a connecting plate.
Ensure that the vertical deviation and the distances between cabinets are within 3 mm after the
cabinets are combined.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
(2) Fixing bolt
5 Installation Guide
(3) Level
Figure
42