Minimum configuration hints for PROFIBUS PA transmitters
The minimum configuration for having AI working needs at least the following settings:
Pressure Transducer Block:
- SCALE_IN: Calibration range (Eng. Units for pressure only)
- LIN_TYPE: Linear, Square Root, Cylindrical Lying Container, Spherical Container, Square Root 3° pow, Square Root 5° pow,
Bidirectional Flow and 22 points table.
Analog Input Block:
- OUT_SCALE: Output range (all allowed Eng. Units)
Minimum configuration hints for FOUNDATION Fieldbus transmitters
The minimum configuration for having AI working and/or moving out from the Out Of Service (OOS) mode needs at least the following
settings:
- CHANNEL: 1=pressure; 2=sensor temp.; 3=static pressure
- XD_SCALE: Calibration range (Eng. Units for pressure only)
- OUT_SCALE: Output range (all allowed Eng. Units)
- L_TYPE: Direct, Indirect or Square Root
Information
For more detailed information about configuration and troubleshooting of FOUNDATION Fieldbus devices, please refer to the
documents listed in "Supplementary Documentation".
If the AI Block cannot be removed from OOS mode, please refere to the below table:
Possible Cause
The target mode is set to OOS
The Configuration Error bit is set in the BLOCK_ERR
The RESOURCE BLOCK is not in AUTO mode
The Block is not scheduled
Set the PV to Zero (for Profibus and FOUNDATION Fieldbus transmitters)
After configuring the transmitters according to the communication protocol, it is necessary to set the PV value to zero.
This operation is tipically used for correction of the mounting position and other influences (line pressure effects). To carry out this
correction the transmitter should be pressure-free, i.e the process connections should be pressure-free or short-circuited. The PV
value can be zeroed by using "set PV to Zero" inside DTM or EDD parametrization menus.
8 SOI/266-XC | 2600T Series Pressure transmitters 266 models
Set the target mode to something different by OOS
CHANNEL different by 0
Set L_Type correctly
Set XD_SCALE unit = TPB Primary Value Range Unit
Set the target mode of the RESOURCE BLOCK to AUTO mode
Design the FB Application correctly and download it to the
devices
Solution