SENTRON PAC3200 is designed for:
● Direct measurement on the system or using voltage transformers. The measuring voltage
● Measuring voltage to 400 V / 690 V (max. 347 V / 600 V for UL) with multi-range power
● Measuring voltage to 289 V / 500 V with extra-low voltage power supply. The device is
Connection types
Five connection types have been provided for connecting two-wire, three-wire or four-wire
systems with balanced or unbalanced load.
Table 3-2
Short code
3P4W
3P3W
3P4WB
3P3WB
1P2W
The input circuit of the device must correspond to one of the connection types listed. Select
the suitable connection type for the purpose.
You can find connection examples in the chapter "Connecting".
Local power supply conditions
Before connecting the SENTRON PAC3200, you must ensure that the local power supply
conditions agree with the specifications on the type plate.
The short code of the connection type must be entered in the device settings at startup. You
can find the instructions for parameterizing the connection type in the chapter "Starting up".
See also
Connection (Page 73)
Set the connection type (Page 95)
Applying the measuring voltage (Page 100)
Applying the measuring current (Page 101)
SENTRON PAC3200
Manual, 02/2008, A5E01168664B-04
inputs of the device measure direct via protective impedances. External voltage
transformers are required to measure higher voltages than the permissible rated input
voltages.
supply. The device is designed for measuring input voltages up to 400 V to the neutral
conductor and 690 V to the external conductor.
designed for measuring input voltages up to 289 V to the neutral conductor and 500 V to
the external conductor.
Available connection types
CAUTION
Connection type
3 phases, 4 conductors, unbalanced load
3 phases, 3 conductors, unbalanced load
3 phases, 4 conductors, balanced load
3 phases, 3 conductors, balanced load
Single-phase AC
Description
3.2 Measuring inputs
23