Display
Type
Resolution
Size W x H
Keyboard
4 function keys F1 to F4 on the front, multiple assignments.

Electromagnetic compatibility

Emission
Immunity

Environmental conditions

The device is suitable for switch panel mounting in accordance with IEC 61554. Operation is
only permissible inside an enclosed dry room.
Temperature range
Relative humidity
Operating altitude above sea level
Degree of pollution
SENTRON PAC3200
Manual, 02/2008, A5E01168664B-04
Monochrome, graphical LC display, light backlighting, dark text and digits
128 x 96 pixels
72 mm x 54 mm
Enclosure
Electrostatic discharge
Electromagnetic fields
Line-frequency magnetic fields
Measuring voltage and supply voltage
Voltage dips
Fast transients
Voltage surges
Cable-borne HF signals
Inputs and outputs, interfaces
Fast transients
Voltage surges
Cable-borne HF interference
fields
Operating temperature
Storage and transport temperature
IEC 61000-6-4 Group 1 Class A or CISPR11
Group 1 Class A or
FCC Part 15 Subpart B Class A.
IEC 61000-6-2 or IEC 61326-1:2005, Table 2.
IEC 61000-4-2:2001-04
IEC 61000-4-3:2006-02
IEC 61000-4-8:2001-03
IEC 61000-4-11:2004-03
EN 61000-4-4:2005-07
EN 61000-4-5:2001-12
EN 61000-4-6:2001-12
IEC 61000-4-4:2004-07
IEC 61000-4-5:2005-11
EN 61000-4-6:2001-12
- 10 °C to + 55 °C
- 25 °C to + 70 °C
95% at 25°C without condensation (normal
conditions)
Up to 2000 m
2
Technical data