Technical data
11.1
Technical data
Device configuration
● 1 slot for optional expansion module
● 1 optically isolated digital input
● 1 optically isolated digital output
● 1 Ethernet interface, RJ45 socket for connecting to the PC or network
Measuring inputs
Only for connection to AC voltage systems
Frequency of the relative fundamental
Measurement rate
Energy
Current, voltage
Waveform
AC voltage input
Device with multi-range power supply
Phase-to-neutral voltage U
Phase-to-phase voltage U
Device with extra-low voltage power supply
Phase-to-neutral voltage U
Phase-to-phase voltage U
Minimum input voltage V
Measuring category
SENTRON PAC3200
Manual, 02/2008, A5E01168664B-04
L-N
L-L
L-N
L-L
ph-n
Input voltage V
I
50/60 Hz
Set automatically
Continuous (zero blind measuring)
Continuous
Values on the display refreshed at least once per second
Sine or distorted
3~ 400 V AC (+ 20 %), max. 347 V for UL
3~ 690 V AC (+ 20 %), max. 600 V for UL
3~ 289 V AC (+ 20 %)
3~ 500 V AC (+ 20 %)
3~ 40 V AC
(in accordance with IEC/UL 61010 Part 1)
V
to 230 V (V
)
I
ph-n
V
to 400 V (V
)
I
ph-ph
V
to 289 V (V
)
I
ph-n
V
to 500 V (V
)
I
ph-ph
11
CAT III
CAT III
CAT III
CAT III
157