PositionMaster EDP300 DIGITAL POSITIONER | CI/EDP300-EN REV. D
... 6 Installation
... Electrical connections
Electrical connection
Connect the positioner (EDP300 Control Unit, housing 1) and
remote position sensor (EDP300 Remote Sensor, housing 2),
while following the instructions below:
The EDP300 Remote Sensor and the EDP300 Control Unit
are adjusted to each other. Ensure that only devices with
the same serial number are connected.
A shielded 3-wire cable with a maximum length of 10 m
(33 ft) must be used for the connection.
Route the cable into the terminal compartment through
the EMC cable glands. Ensure that the shielding is
secured correctly in the EMC cable glands.
Connect the cables in accordance with the electrical
connections and tighten the screws of the terminals so
that they are hand-tight.
Use wire end ferrules when connecting.
The electrical connections of the EDP300 Control Unit
and the optional modules are carried out as described in
Connection on the device on page 35.
If the EDP300 Control Unit is fastened so that it is it non-
conductive, the housing must be grounded
(EDP300 Control Unit and EDP300 Remote Sensor
housing with the same electric potential); otherwise
control deviations could occur with regard to analog
position feedback.
In the EDP300 Remote Sensor in IP rating IP 66, pre-
tighten the cover screws by applying approx. 50 Ncm
(0.44 lbf-in) cross-wise and then tighten by applying
200 Ncm (1.77 lbf-in).
The pneumatic outputs to the actuator must be
connected using pneumatic lines with a minimum
diameter of 6 mm.