323561c.fm Page 9 Thursday, August 11, 2005 4:02 PM
Safe Mode Switch
Console Out Switch
IP Reset Switch
© National Instruments Corporation
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
The position of the Safe Mode switch determines whether the embedded
LabVIEW Real-Time engine launches when the controller boots. If the
switch is in the OFF position, the LabVIEW Real-Time engine launches.
Keep this switch in the OFF position during normal operation. If the switch
is in the ON position when the controller boots, the controller launches only
the essential services required for updating its configuration and installing
software. The LabVIEW Real-Time engine does not launch.
Push the Safe Mode switch to the ON position if the software on the
controller is corrupted. If there is no software installed on the controller, the
controller automatically boots into safe mode regardless of the position of
the safe mode switch. The Safe Mode switch must be in the ON position to
reformat the drive on the controller. Refer to the Measurement &
Automation Explorer Help for more about installing software on a
controller and the reformatting the drive on the controller.
With a serial-port terminal program, you can use the Console Out switch to
read the IP address and BIOS version of the controller. Connect the serial
port on the controller to a computer. Push the switch to the ON position.
Make sure that the serial-port terminal program is configured to the
following settings:
•
9,600 bits per second
•
Eight data bits
•
No parity
•
One stop bit
The serial-port terminal program displays the IP address and BIOS version.
Keep this switch in the OFF position during normal operation.
Push the IP Reset switch to the ON position and reboot the controller to
reset the IP address of the controller to
local subnet and the IP Reset switch is in the ON position, the controller
appears in MAX with IP address
IP address for the controller in MAX. Refer to the
Configuration of the Controller
resetting the IP address. You also can push this switch to the ON position
to unlock a controller that was previously locked in MAX.
9
. If the controller is on your
0.0.0.0
. You can configure a new
0.0.0.0
Resetting the Network
section for more information about
cRIO-9002/9004 Operating Instructions