ABB EDS500 Series Function Manual page 66

Ethernet & dsl switches
Hide thumbs Also See for EDS500 Series:
Table of Contents

Advertisement

IEC 60870-5-101 and IEC 60870-5-104
For default values for the addresses of the information objects refer to "Tab. 27: Information
objects".
Object / Function
System – Warning
System – Alarm
Console0 – RTS
(Input)
Console0 – CTS
(output)
Console0 – DCD
(output)
Link state interfaces
Speed interfaces
Signal quality inter-
faces
Port state interfaces
Table 27:
Information objects
66
State / Value range
OFF: normal state
ON: Warning imminent
OFF: normal state
ON: Alarm imminent
OFF: open
OFF: -25 ... 0 V
ON: 3 ... 25 V
OFF: -2.5 ... -5 V
ON: 2.5 ... 5 V
max. 5 mA
OFF: -2.5 ... -5 V
ON: 2.5 ... 5 V
max. 5 mA
OFF: no link
ON: link
Value in bps
>= 2147483648: value
is invalid
16,0 dB >= value 160
>= 8388608: value is
invalid
0x: Port blocked
1x: Port learns and
blocked
2x: Port forwards
x0: Port is deactivated
x1: Port roll is Root
x2: Port roll is Desig-
nated
x3: Port roll is Alter-
nate
x4: Port roll is Backup
x5: Port roll is Master
Pre-set object
address
1
2
3
4
5
from 128
from 160
from 192
from 224
Functions
ASDU data type
1
(Single message)
1
(Single message)
1 / 15
(Single message /
counter)
1
(Single message)
1
(Single message)
1
(Single message)
7
(Bit pattern 32 bit)
11
(Measured value,
scaled)
5
(Level setting mes-
sage)
1KGT151021 V000 1