Connection Examples; Start/Stop; Pulse Start/Stop - GE AF-650 GP Operating Instructions Manual

General purpose drive high power 460/575/690v 125hp and above
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Installation

3.5 Connection Examples

3.5.1 Start/Stop

Terminal 18 = E-01 Terminal 18 Digital Input [8] Start

3.5.2 Pulse Start/Stop

Terminal 18 = E-01 Terminal 18 Digital Input [9] Latched
start
Terminal 27= E-03 Terminal 27 Digital Input [6] Stop inverse
AF-650 GP High Power Operating Instructions
3.5.3 Speed Up/Down
Terminals 29/32 = Speed up/down
3.5.4 Potentiometer Reference
Voltage reference via a potentiometer
Terminal 18 = E-01 Terminal 18 Digital Input Start
[9] (default)
Terminal 27 = E-03 Terminal 27 Digital Input
Freeze reference [19]
Terminal 29 = E-04 Terminal 29 Digital Input
Speed up [21]
Terminal 32 = E-05 Terminal 32 Digital Input
Speed down [22]
Reference Source 1 = [1] Analog input 53 (default)
Terminal 53, Low Voltage = 0V
Terminal 53, High Voltage = 10V
Terminal 53, Low Ref./Feedback = 0 RPM
Terminal 53, High Ref./Feedback = 1500 RPM
Switch S201 = OFF (U)