Instructions; Abbreviations And Definitions; Network Connection - GE AF-600 FP Metasys Operating Instructions Manual

Table of Contents

Advertisement

2 Instructions

2.1.1 Abbreviations and Definitions

Abbreviations and definitions
ACK
Acknowledge
ADF
Internal Floating Points
ADI
Internal Integers
AI
Analog Inputs
AO
Analog Outputs
BI
Binary Inputs
BO
Binary Outputs
COS
Change Of State
HPFB
High Performance Field Network
JCI
Johnson Controls Inc. developers of the METASYS N2 protocol
N2
METASYS N2
N2 master
A N2 master is either a PC with JCI software or a dedicated JCI controller
NAK
Not acknowledged
NPA
N2 Point Address (Each N2 Point Type has a address range from 0 to 255)
NPT
N2 Point Type
PAR
Parameter Number

2.1.2 Network Connection

Connect signal wires to terminal 68 (N+) and terminal 69 (N-) on main control board of the drive. If shielded cabling is used, connect one end of the shield to
terminal 61. This terminal is connected to ground via an internal RC link. It is highly recommended to use twisted-pair cables to reduce the differential mode
interference between the conductors
Torque Specifications:
Control wire:
4.5 in.lb. (0.5 Nm)
18 - 24 AWG, shielded, twisted pair
AF-600 FP Metasys