The Timing Of The Maintenance; The Correct Operating Temperature; Insulation Resistance Test - ABB AMA Series Manual

For induction motors and generators
Table of Contents

Advertisement

7.6.2 The timing of the maintenance

7.6.3 The correct operating temperature

***Following paragraph for cooling type: Open air

7.6.4 Insulation resistance test

3BFP 000 050 R0101 REV E
Spray-varnish equipment, the frame of the machine, and the windings should be earthed
during spray varnishing
Take necessary precautions when working in pits and cramped places
Only people trained to do high-voltage work can carry out a voltage test
Do not smoke, eat, or drink at the work site.
For a test record for winding maintenance, see Appendix COMMISSIONING REPORT.
There are three main principles for timing the winding maintenance:
Maintenance of the windings should be arranged according to other machine maintenance
Maintenance should be performed only when necessary
Important machines should be serviced more often than the less important ones. This also
applies to windings that become contaminated rapidly and to heavy drives.
NOTE: As a thumb rule, an insulation resistance test should be made once a year. This should
suffice for most machines in most operating conditions. Other tests should only be
conducted if problems arise.
A maintenance program for the complete machine, including windings, is presented in Chapter
7.3 Maintenance program. This maintenance program however, should be adapted to the
customer's particular circumstances, i.e. servicing of other machines and operating conditions as
long as recommended servicing intervals are not exceeded.
The correct temperature of the windings is ensured by keeping the exterior surfaces of the
machine clean, by seeing to the correct operation of the cooling system and by monitoring the
temperature of the coolant. If the coolant is too cold, water may condense inside the machine.
This can wet the winding and deteriorate the insulation resistance.
For air-cooled machines, it is important to monitor the cleanliness of the air filters. The cleaning
and change interval of the air filters should be planned according to the local operating
environment.
The stator operating temperatures must be monitored with resistance temperature detectors.
Significant temperature differences among the detectors could be a sign of damage in the
windings. Make sure that the changes are not caused by the drifting of the measuring channel.
During general maintenance work and before the machine is started up for the first time or after
a long period of standstill, the insulation resistance of stator and rotor windings must be
measured.
The insulation resistance measurement provides information about the humidity and dirtiness of
the insulation. Based upon this information, correct cleaning and drying actions can be
determined.
Manual for Induction Motors and Generators
Maintenance - 79