Oil Change Schedule For Mineral Oils - ABB AMA Series Manual

For induction motors and generators
Table of Contents

Advertisement

Environmentally
Benign Oils:
Aral
Mobil
Shell
Mineral Oils:
Aral
BP
Castrol
Chevron
Esso
Klüber
Mobil
Shell
Total

7.5.2.5 Oil change schedule for mineral oils

3BFP 000 050 R0101 REV E
ISO VG 22
ISO VG 32
Viscosity 22 cSt
Viscosity 32 cSt
at 40 °C
at 40 °C
Vitam EHF 22
EAL
-
Hydraulic Oil 32
Naturelle
-
HF-E 32
Vitam GF 22
Vitam GF 32
Energol CS 22
Energol CS 32
Hyspin AWS 22 Hyspin AWS 32
Texaco Rando
Texaco Rando
HDZ 22
HDZ 32
Nuto H 22
Terrestic T 32
LAMORA HLP
Velocite Oil No.
DTE Oil Light
10
Tellus S 22
Tellus S 32
Azolla ZS 22
Azolla ZS 32
For self-lubricated bearings cleaning intervals with oil changes of approximately 8000
operating hours are recommended and approx. 20000 operating hours for bearings with oil
circulation systems.
Shorter oil change intervals may be necessary in case of frequent start-ups, high oil
temperatures or excessively high contamination due to external influences.
The correct oil change interval can be found on the bearing plate and dimensional drawing, see
Chapter 2.1.2 Bearing plate.
Manual for Induction Motors and Generators
ISO VG 46
Viscosity 46
cSt at 40 °C
Vitam EHF
-
46
EAL
Hydraulic Oil
46
Naturelle
HF-E 46
Vitam GF 46 Vitam GF 68 Degol CL 100 T
Energol CS
46
Hyspin AWS
46
Texaco
Rando HDZ
46
Terrestic T
46
LAMORA
32
HLP 46
DTE Oil
Medium
Tellus S 46
Azolla ZS 46 Azolla ZS 68
ISO VG 68
ISO VG 100
Viscosity 68
Viscosity 100
cSt at 40 °C
cSt at 40 °C
-
-
Naturelle
HF-E 68
Energol CS 68 Energol CS 100
Hyspin AWS
Hyspin AWS
68
100
Texaco Rando
Texaco Rando
HDZ 68
HDZ 100
Terrestic T 68
LAMORA HLP
CRUCOLAN
68
100
DTE Oil
Heavy
DTE Oil Heavy
Medium
Tellus S 68
Tellus S 100
Azolla ZS 100
Maintenance - 71
-
-
-
-

Hide quick links:

Advertisement

Table of Contents
loading