E NG INEE R ING
Connecting GOOSE sender data to a protection relay application in PCM600
Step 1 / 3
Adding GOOSERCV function block with Application Configuration Tool. Give the GOOSERCV
block application-specific user-defined names to distinguish between different blocks when
making GOOSE connections in the Signal Matrix tool.

Figure 52: Adding a GOOSERCV function block in the Application Configuration Tool

Step 2 / 3
Creating GOOSERCV block connection into the application

Figure 53: Creating GOOSERCV block connection to a new variable

Step 3 / 3
Mapping of GOOSE sender data into the corresponding GOOSERCV function block in Signal
Matrix

Figure 54: Signal Matrix

1V LG 5 000 07 E
S TAT IO N BU S (G O OS E)
41